Table 7 – Space Sensor Mode
|
|
|
|
|
|
| ||
| TB1 TERMINAL |
|
| FIELD CONNECTION |
| INPUT SIGNAL | ||
|
| 1 |
|
|
|
| Analog (10k thermistor) | |
|
| 2 |
|
|
| RMTOCC |
| Discrete, 24VAC |
|
| 3 |
|
|
|
| Analog (10k thermistor) | |
|
| 4 |
|
|
| CMPSAFE |
| Discrete, 24VAC |
|
| 5 |
|
|
|
| Analog (10k thermistor) | |
|
| 6 |
|
|
| FSD |
| Discrete, 24VAC |
|
| 7 |
|
|
|
| Analog, 24VDC | |
|
| 8 |
|
|
| SPS |
| Discrete, 24VAC |
|
| 9 |
|
|
|
| Analog, | |
|
| 10 |
|
|
| FILTER |
| Discrete, 24VAC |
|
| 11 |
|
|
| Analog, | ||
|
| 12 |
|
|
| CCN + (RED) |
| Digital, , 5VDC |
|
| 13 |
|
|
|
| Analog, | |
|
| 14 |
|
|
| CCN Gnd (WHT) |
| Digital, 5VDC |
|
| 15 |
|
|
| AUX OUT(Power Exhaust) |
| (Output)Discrete 24VAC |
|
| 16 |
|
|
| CCN |
| Digital, 5VDC |
LEGEND: |
|
|
|
|
|
|
| |
T55 |
| Space Temperature Sensor |
| |||||
T56 |
| Space Temperature Sensor |
| |||||
CCN |
| Carrier Comfort Network (communication bus) |
| |||||
CMPSAFE | Compressor Safety |
|
|
| ||||
FILTER | Dirty Filter Switch |
|
|
| ||||
FSD |
| Fire Shutdown |
|
|
| |||
IAQ |
| Indoor Air Quality (CO2) |
| |||||
OAQ |
| Outdoor Air Quality (CO2) |
| |||||
RH |
| Relative Humidity |
|
|
| |||
SFS |
| Supply Fan Status |
|
|
| |||
|
|
|
|
|
| Table 8 – Thermostat Mode |
| |
|
|
|
|
| ||||
| TB1 TERMINAL |
| FIELD CONNECTION | INPUT SIGNAL | ||||
|
| 1 |
|
|
| RAT SEN | Analog (10k thermistor) | |
|
| 2 |
|
|
| G | Discrete, 24VAC | |
|
| 3 |
|
|
| RAT SEN | Analog (10k thermistor) | |
|
| 4 |
|
|
| Y1 | Discrete, 24VAC | |
|
| 5 |
|
|
|
|
|
|
|
| 6 |
|
|
| Y2 | Discrete, 24VAC | |
|
| 7 |
|
|
| Analog, 24VDC | ||
|
| 8 |
|
|
| W1 | Discrete, 24VAC | |
|
| 9 |
|
|
| Analog, | ||
|
| 10 |
|
|
| W2 | Discrete, 24VAC | |
|
| 11 |
|
|
| Analog, | ||
|
| 12 |
|
|
| CCN + (RED) | Digital, 5VDC | |
|
| 13 |
|
|
| Analog, | ||
|
| 14 |
|
|
| CCN Gnd (WHT) | Digital, 5VDC | |
|
| 15 |
|
|
| AUX OUT (Power Exhaust) | (Output) Discrete 24VAC | |
|
| 16 |
|
|
| CCN | Digital, 5VDC | |
LEGEND: |
|
|
|
|
|
|
| |
CCN | Carrier Comfort Network (communication bus) |
| ||||||
G | Thermostat Fan |
|
|
| ||||
IAQ | Indoor Air Quality (CO2) |
|
|
| ||||
OAQ | Outdoor Air Quality (CO2) |
|
|
| ||||
RAT | Return Air Temperature |
|
|
| ||||
RH | Relative Humidity |
|
|
| ||||
W1 | Thermostat Heat Stage 1 |
|
|
| ||||
W2 | Thermostat Heat Stage 2 |
|
|
| ||||
Y1 | Thermostat Cool Stage 1 |
|
|
| ||||
Y2 | Thermostat Cool Stage 2 |
|
|
|
50TC
27