Image 31
Air Flow

Chapter 2 Preparation for Installation

Power Requirements

Air Flow

Note The air flows from front to back through the Cisco SFS 7000P and SFS 7000D Server Switches. (See Figure 2-1.)

Figure 2-1 Air Flow Direction in the Cisco SFS 7000P and SFS 7000D Server Switches

Back

181224

Front

Follow these guidelines to ensure proper airflow:

Maintain ambient airflow throughout the data center to ensure normal operation.

If installing in an enclosed cabinet, ensure that the cabinet has adequate ventilation, and allow at least 2.5 inches (6.4 cm) of clearance between the chassis vents and the cabinet wall.

If placing the switch adjacent to a device that exhausts air towards the switch, the horizontal distance between the devices should be a minimum of 6 inches (15.2 cm).

Ensure that cables do not obstruct the airflow through the chassis.

Consider heat dissipation of all equipment when determining the air-conditioning requirements, as specified in the hardware installation guide. When evaluating airflow requirements, consider that hot air generated by equipment at the bottom of the rack can be drawn into the intake ports of the equipment above.

Power Requirements

Follow these requirements when preparing your site for the switch installation:

In systems configured with two power supplies, connect each of the two power supplies to a separate input power source. If you fail to do this, your system might be susceptible to total power failure due to a fault in the external wiring or a tripped circuit breaker.

To prevent a loss of input power, be sure that the total maximum load on each source circuit is within the current ratings of the wiring and breakers.

The AC power receptacles used to plug in the chassis must be the grounding type. The grounding conductors that connect to the receptacles should connect to protective earth ground at the service equipment.

Cisco SFS 7000P and SFS 7000D InfiniBand Server Switches Hardware Installation Guide

 

OL-10853-01

2-5

 

 

 