2: BladeManager Installation

Rack Mounting Guidelines

When rack-mounting the BladeManager, consider the following:

Ensure the room temperature is below 35o C (95o F).

If you install the BladeManager in a closed or multi-rack assembly, the operating ambient temperature of the rack environment may be greater than the room ambient temperature. Ensure that you install the equipment in an environment compatible with the manufacturer’s maximum rated ambient temperature.

Do not block any air vents. Usually, 15 cm (6 in.) of air space provides proper airflow.

Plan the device installation starting from the bottom of the rack cabinet.

Install the heaviest device in the bottom of the rack cabinet.

Do not extend more than one device out of the rack cabinet at the same time.

Connect all power cords to properly wired and grounded electrical outlets.

Maintain reliable earthing of rack mounted equipment by inspecting supply connections other than direct connections to the branch circuit such as power strips or extension cords.

Do not overload the power outlet when installing multiple devices in the rack.

Remove the rack doors and side panels to provide easier access during installation.

The slide rails in the kit come preset to the correct length for installing in an IBM rack cabinet and they are adjustable for other rack cabinets.

The slide rails are marked RIGHT/FRONT and LEFT/FRONT for proper placement on the rack-cabinet flanges.

Ensure that the equipment is mounted or loaded evenly to prevent a potentially hazardous condition.

Do not place any object weighing more than 50 kg (110 lb) on top of rack- mounting devices.