Environmental
NOTE: For additional information about environmental measurements for specific system
configurations, see dell.com/environmental_datasheets.
Temperature
Operating Continuous operation: 10 °C to 35 °C (50 °F to 95 °F) at
20% to 80% relative humidity (RH), with 26 °C
maximum dew point. De-rate maximum allowable dry
bulb temperature at 1 °C/300 m (1 °F per 550 ft) above
900 m (2952.75 ft).
NOTE: For information on supported expanded
operating temperature range and configurations,
see the Owner's Manual at dell.com/support/
manuals.
Storage –40 °C to 65 °C (–40 °F to 149 °F) with a maximum
temperature gradation of 20 °C per hour
Relative humidity
Operating 20% to 80% (noncondensing) with maximum humidity
gradation of 10% per hour
Storage 5% to 95% at a maximum wet bulb temperature of 38
°C (100.4 °F)
Maximum vibration
Operating 0.26 Grms at 5 Hz to 350 Hz in operational orientation
Storage 1.88 Grms at 10 Hz to 500 Hz for 15 minutes (all six sides
tested)
Maximum shock
Operating One shock pulse in the positive z axis of the system at
31 G for 2.6 ms in the operational orientation
Storage Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) at 71 G for up to 2 ms
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 22 G faired square wave pulse with
velocity change at 200 inches/second (508
centimeters/second)
Altitude
Operating Maximum 3000 m (9,842 ft)
Storage Maximum 12192 m (40,000 ft)
Airborne contaminant level
Class G1 as defined by ISA-S71.04-1985
53