zSet up DVPCOPM-SL and IFD9503 according to the table below. For how to operate IFD9503, please refer to Chapter 13.

Module

Node address

 

 

Baud rate (bps)

DVPCOPM-SL

01

 

 

 

1M

 

 

 

 

 

 

IFD9503

02 (connected to ASD-B)

 

 

1M

 

 

 

 

 

IFD9503

03 (connected to DVP-12SA)

 

1M

 

 

 

 

 

 

Set up ASD-B as follows:

 

 

 

 

 

 

 

 

 

 

 

Parameter

Set value

 

 

 

Explanation

P1-01

02

 

 

 

Control mode: speed mode

 

 

 

 

 

P1-09

100 (rpm)

 

 

Internal speed command 1 (SP1)

 

 

 

 

 

P1-10

300 (rpm)

 

 

Internal speed command 2 (SP2)

 

 

 

 

 

P1-11

500 (rpm)

 

 

Internal speed command 3 (SP3)

 

 

 

 

 

 

P2-10

101

 

 

 

Function of DI1: Servo on

 

 

 

 

 

 

P2-11

114

 

 

 

Functin of DI2: SPD0

 

 

 

 

 

 

P2-12

115

 

 

 

Functino of DI3: SPD1

 

 

 

 

P2-18

102

 

Function of DO1: Output when servo on

 

 

 

 

 

P3-00

1

 

 

Modbus communication address

 

 

 

 

 

 

P3-01

5 (115,200 bps)

 

 

 

Modbus baud rate

 

 

 

 

 

 

P3-02

1 (7,E,1)

 

 

 

Modbus data format

 

 

 

 

P3-06

3F

 

DI1 ~ DI6 controlled by communication

 

 

 

 

 

 

zConstructing the CANopen network following the figure below.

DVP-PS02 DVPCOPM-SL DVP28SV

DVPCOPMDVP28SV

L

N

0V

RUN

CANopen

network configuration tool

STOP

CANopen

Node 2

PORT1

P O RT2

 

 

 

 

IFD9503

ASD-B

Node 1

RS-232

Node 3

PORT1

PO RT2

L

N

0V

AS2 P1- VD

DVP-08ST

DVP-12SA DVP-08ST

DVP-PLC Application Manual

9