Emerson Process Management 2051 Electrical, Conduit Installation, Rosemount, Reference Manual

Models: 2051

1 152
Download 152 pages 41.56 Kb
Page 31
Image 31
ELECTRICAL

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

ELECTRICAL

NOTE

CONSIDERATIONS

Make sure all electrical installation is in accordance with national and local code

 

requirements.

Conduit Installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If all connections are not sealed, excess moisture accumulation can damage the transmitter. Make sure to mount the transmitter with the electrical housing positioned downward for drainage. To avoid moisture accumulation in the housing, install wiring with a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit connections or the transmitter housing.

Figure 2-12. Conduit Installation Diagrams.

Possible

Conduit Line

Positions

Sealing

Compound

CORRECT

Recommended conduit connections are shown in Figure 2-12.

Conduit

Lines

Sealing

Compound

Possible

Conduit Line

Positions

CORRECTINCORRECT

2-21

Page 31
Image 31
Emerson Process Management 2051 manual Electrical, Conduit Installation, Rosemount, Reference Manual, Considerations