Emerson Process Management 2051 Static Pressure Limit Burst Pressure Limits, Temperature Limits

Models: 2051

1 152
Download 152 pages 41.56 Kb
Page 79
Image 79
Static Pressure Limit

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

2051L

Limit is flange rating or sensor rating, whichever is lower (see Table A-2). Table A-2. 2051L Flange Rating

Standard

Type

CS Rating

SST Rating

 

 

 

 

ANSI/ASME

Class 150

285 psig

275 psig

 

 

 

 

ANSI/ASME

Class 300

740 psig

720 psig

At 100 °F (38 °C), the rating decreases with

 

increasing temperature.

 

 

 

 

 

DIN

PN 10–40

40 bar

40 bar

DIN

PN 10/16

16 bar

16 bar

At 248 °F (120 °C), the rating decreases

with increasing temperature.

Static Pressure Limit

Burst Pressure Limits

Temperature Limits

2051CD

Operates within specifications between static line pressures of -14.2 psig (0.034 bar) and 3626 psig (250 bar)

• For Option Code P9, 4500 psig (310,3 bar)

Range 1: 0.5 psia to 2000 psig (34 mbar and 137,9 bar)

2051C Coplanar or traditional process flange

• 10000 psig (689,5 bar)

2051T

Ranges 1–4: 11000 psi (758,4 bar)

Range 5: 26000 psi (1792,64 bar)

Ambient

–40 to 185 °F (–40 to 85 °C)

With LCD display(1): –40 to 175 °F (–40 to 80 °C)

Storage

–50 to 230 °F (–46 to 110 °C)

With LCD display: –40 to 185 °F (–40 to 85 °C)

(1)LCD display may not be readable and LCD updates will be slower at temperatures below -4 °F (-20 °C).

Process Temperature Limits

At atmospheric pressures and above.

Table A-3. 2051 Process Temperature Limits

2051C

Silicone Fill Sensor(1)

 

with Coplanar Flange

–40 to 250 °F (–40 to 121 °C)(2)

with Traditional Flange

–40 to 300 °F (–40 to 149 °C)(2)

with Level Flange

–40 to 300 °F (–40 to 149 °C)(2)

with 305 Integral Manifold

–40 to 300 °F (–40 to 149 °C)(2)

Inert Fill Sensor(1)

0 to 185 °F (–18 to 85 °C)(3)

2051T (Process Fill Fluid)

 

 

Silicone Fill Sensor(1)

–40 to 250 °F (–40 to 121 °C)(2)

Inert Fill Sensor(1)

–22 to 250 °F (–30 to 121 °C)(2)

2051L Low-Side Temperature Limits

 

 

Silicone Fill Sensor(1)

–40 to 250 °F (–40 to 121 °C)(2)

A-7

Page 79
Image 79
Emerson Process Management 2051 manual Static Pressure Limit Burst Pressure Limits, Temperature Limits, Rosemount