1.Put Resource block into "OOS" (Out of Service).

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

1.Put Resource block into "OOS" (Out of Service).

2.Go to the parameter called "SELF_TEST" and write the value Self test (0x2).

3.Observe the LCD screen when you are doing this. All of the segments should light up.

4.Put the Resource block back into "AUTO".

Table 5-10. LCD Transducer

Block BLOCK_ERR messages

Condition Name and Description

 

 

Other

 

 

 

Out of Service: The actual mode is out of service.

 

 

 

 

 

Symptom

 

Possible Causes

Recommended Action

 

 

 

The LCD displays “DSPLY#INVLID.” Read the

One or more of the display parameters are

See “LCD Transducer Block” on

BLOCK_ERR and if it says “BLOCK

 

not configured properly.

page 2-16.

CONFIGURATION” perform the Recommended Action

 

 

 

 

 

“2051” is being displayed or not all of the values are

The LCD block parameter

See “LCD Transducer Block” on

being displayed.

 

“DISPLAY_PARAMETER_SELECT is not

page 2-16.

 

 

properly configured.

 

 

 

 

 

The display reads OOS

The resource and or the LCD Transducer

 

block are OOS.

 

 

The display is hard to read.

Some of the LCD segments may have

 

gone bad.

 

Device is out o the temperature limit for the

 

LCD. (-20 to 80 °C)

 

 

Verify that both blocks are in “AUTO,”

See XXXX (Self Test). If some of the segment is bad, replace the LCD.

Check ambient temperature of the device.

5-8

Page 68
Image 68
Emerson Process Management 2051 manual Rosemount, Reference Manual, 00809-0200-4101,Rev AA July, 10.LCD Transducer