Emerson Process Management 2051 manual Rosemount, Reference Manual, Parameters and Descriptions

Models: 2051

1 152
Download 152 pages 41.56 Kb
Page 137
Image 137
Manual background

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

Parameters and Descriptions

The table below lists all of the configurable parameters of the Resource Block, including the descriptions and index numbers for each.

 

Index

 

Parameter

Number

Description

 

 

 

ACK_OPTION

38

Selection of whether alarms associated with the function block will be

 

 

automatically acknowledged.

 

 

 

ALARM_SUM

37

The current alert status, unacknowledged states, unreported states, and disabled states

 

 

of the alarms associated with the function block.

ALERT_KEY

04

The identification number of the plant unit.

 

 

 

BLOCK_ALM

36

The block alarm is used for all configuration, hardware, connection failure or system

 

 

problems in the block. The cause of the alert is entered in the subcode field. The first alert

 

 

to become active will set the Active status in the Status parameter. As soon as the

 

 

Unreported status is cleared by the alert reporting task, another block alert may be

 

 

reported without clearing the Active status, if the subcode has changed.

BLOCK_ERR

06

This parameter reflects the error status associated with the hardware or software

 

 

components associated with a block. It is a bit string, so that multiple errors may be

 

 

shown.

 

 

 

CONFIRM_TIME

33

The time between retries of alert reports.

CYCLE_SEL

20

Used to select the block execution method for this resource. The 2051 supports the

 

 

following:

 

 

Scheduled: Blocks are only executed based on the function block schedule.

 

 

Block Execution: A block may be executed by linking to another blocks completion.

 

 

 

CYCLE_TYPE

19

Identifies the block execution methods available for this resource.

DD_RESOURCE

09

String identifying the tag of the resource which contains the Device Description for

 

 

this resource.

 

 

 

DD_REV

13

Revision of the DD associated with the resource - used by an interface device to locate

 

 

the DD file for the resource.

define_write_lock

60

Enumerated value describing the implementation of the WRITE_LOCK.

 

 

 

detailed_status

55

Indicateds the state of the transmitter. See Resource Block detailed status codes.

DEV_REV

12

Manufacturer revision number associated with the resource - used by an interface device

 

 

to locate the DD file for the resource.

 

 

 

DEV_TYPE

11

Manufacturer’s model number associated with the resource - used by interface devices to

 

 

locate the DD file for the resource.

download_mode

67

Gives access to the boot block code for over-the-wire downloads.

 

 

0 = Uninitialized

 

 

1 = Run mode

 

 

2 = Download mode

 

 

 

DRAIN_VENT_MAT

75

Type of material of the drain vents on the flange. See drain vent material codes.

 

 

2 = 316 Stainless Steel

 

 

3 = Hastelloy C

 

 

4 = Monel

 

 

251 = None

 

 

252 = "Unknown"

 

 

253 = "Special"

FEATURES

17

Used to shows supported resource block options.

 

 

 

FEATURES_SEL

18

Used to show selected resource block options. The 2051 supports the following:

 

 

Unicode: Tells host to use unicode for string values

 

 

Reports: Enables alarms. Must be set for alarming to work

 

 

Software Lock: Software write locking enabled but not active. WRITE_LOCK must be set

 

 

to activate.

 

 

Hardware Lock: Hardware write locking enabled but not active. WRITE_LOCK follows the

 

 

status of the security switch.

final_assembly_number

49

Final Assembly Number is placed on the neck label.

C-7

Page 137
Image 137
Emerson Process Management 2051 Rosemount, Reference Manual, Parameters and Descriptions, 00809-0200-4101,Rev AA July