Integral Manifold Operation

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

Integral Manifold Operation

Three-valve configuration shown.

In normal operation the two isolate valves between the process and instrument ports will be open and the equalizing valve(s) will be closed.

H

 

L

Drain/

 

Drain/

 

 

Vent

 

Vent

 

 

Valve

Equalize

Valve

 

 

 

 

(closed)

 

Isolate

Isolate

(open)

(open)

 

Process

To zero the 2051, close the isolate valve to the low pressure (downstream side) of the transmitter first.

H

L

Drain/

 

Vent

 

Valve

Equalize

 

 

(closed)

Isolate

Isolate

(open)

(closed)

 

Process

Next, open the center (equalize) valve(s) to equalize the pressure on both sides of the transmitter.

H

 

L

Drain/

 

Drain/

 

 

Vent

 

Vent

 

 

Valve

Equalize

Valve

 

 

 

 

(open)

 

Isolate

 

Isolate

(open)

 

(closed)

 

Process

 

2-29