Emerson Process Management 2051 manual Parameters and Descriptions, Rosemount, Reference Manual

Models: 2051

1 152
Download 152 pages 41.56 Kb
Page 132
Image 132
Parameters and

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

Parameters and

Descriptions

 

Index

 

 

Parameter

Number

Description

 

 

 

ALERT_KEY

04

The identification number of the plant unit.

 

 

 

BLOCK_ALM

08

The block alarm is used for all configuration, hardware, connection failure or system

 

 

problems in the block. The cause of the alert is entered in the subcode field. The first

 

 

alert to become active will set the Active status in the Status parameter. As soon as

 

 

the Unreported status is cleared by the alert reporting task, another block alert may be

 

 

reported without clearing the Active status, if the subcode has changed.

BLOCK_ERR

06

This parameter reflects the error status associated with the hardware or software

 

 

components associated with a block. It is a bit string, so that multiple errors may be

 

 

shown.

 

 

 

CAL_MIN_SPAN

18

The minimum calibration span value allowed. This minimum span information is

 

 

necessary to ensure when calibration is done, the two calibrated points are not too

 

 

close together.

CAL_POINT_HI

16

The highest calibrated value.

 

 

 

CAL_POINT_LO

17

The lowest calibrated value.

CAL_UNIT

19

The device description engineering units code index for the calibration values.

 

 

Valid calibration units are the following:

 

 

1130

= Pa

 

 

1133

= kPa

 

 

1137

= bar

 

 

1138

= mbar

 

 

1139

= torr

 

 

1140

= atm

 

 

1141

= psi

 

 

1144

= g/cm2

 

 

1145

= kg/cm2

 

 

1148

= inH2O @ 68 °F

 

 

1151

= mmH2O @ 68 °F

 

 

1154

= ftH2O @ 68 °F

 

 

1156

= inHg @ 0 °C

 

 

1158

= mmHg @ 0 °C

 

 

 

COLLECTION_DIRECTORY

12

A directory that specifies the number, starting indices, and DD Item ID's of the data

 

 

collections in each transducer within a transducer block.

FACT_CAL_RECALL

33

Recalls the sensor calibration set at the factory.

 

 

 

MODE_BLK

05

The actual, target, permitted, and normal modes of the block.

 

 

Target: The mode to “go to”

 

 

Actual: The mode the “block is currently in”

 

 

Permitted: Allowed modes that target may take on

 

 

Normal: Most common mode for target

mODULE_TYPE

34

Indicates the type of sensor module.

 

 

0 = Standard coplanar (C)

 

 

1 = Standard threaded (T)

 

 

2 = Level Coplanar (L)

 

 

3 = Reference class coplanar (P)

 

 

4 = High temp. conventional (H)

 

 

252 = Unknown

 

 

 

PRIMARY_VALUE

14

The measured value and status available to the function block.

 

 

 

 

C-2

Page 132
Image 132
Emerson Process Management 2051 manual Parameters and Descriptions, Rosemount, Reference Manual