ANALOG INPUT (AI) FUNCTION BLOCK

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

ANALOG INPUT (AI) FUNCTION BLOCK

Configure the AI block

Configure the AI block A minimum of four parameters are required to configure the AI Block. The parameters are described below with example configurations shown at the end of this section.

CHANNEL

Select the channel that corresponds to the desired sensor measurement. The 2051 measures both pressure (channel 1) and sensor temperature (channel 2).

Table 3-1. I/O Channel Definitions

Channel Number

Channel Description

 

 

1

differential pressure in AI.XD_SCALE units

 

 

2

sensor temperature in AI.XD_SCALE units

 

 

L_TYPE

The L_TYPE parameter defines the relationship of the sensor measurement (pressure or sensor temperature) to the desired output of the AI Block (e.g. pressure, level, flow, etc.). The relationship can be direct, indirect, or indirect square root.

Direct

Select direct when the desired output will be the same as the sensor measurement (pressure or sensor temperature).

Indirect

Select indirect when the desired output is a calculated measurement based on the sensor measurement (e.g. a pressure measurement is made to determine level in a tank). The relationship between the sensor measurement and the calculated measurement will be linear.

Indirect Square Root

Select indirect square root when the desired output is an inferred measurement based on the sensor measurement and the relationship between the sensor measurement and the inferred measurement is square root (e.g. flow).

XD_SCALE and OUT_SCALE

The XD_SCALE and OUT_SCALE each include three parameters: 0%, 100%, and, engineering units. Set these based on the L_TYPE:

L_TYPE is Direct

When the desired output is the measured variable, set the XD_SCALE to the “Primary_Value_Range”. This is found in the Sensor Transducer Block. Set OUT_SCALE to match XD_SCALE.

L_TYPE is Indirect

When an inferred measurement is made based on the sensor measurement, set the XD_SCALE to represent the operating range that the sensor will see in the process. Determine the inferred measurement values that correspond to the XD_SCALE 0 and 100% points and set these for the OUT_SCALE.

3-5

Page 49
Image 49
Emerson Process Management 2051 manual Analog Input Ai Function Block, Configure the AI block, Rosemount, Reference Manual