The manifold valves are now in the proper configuration for zeroing the transmitter. To return the transmitter to service, close the equalizing valve(s) first.

H

 

L

Drain/

 

Drain/

 

 

Vent

 

Vent

 

 

Valve

Equalize

Valve

 

 

 

 

(closed)

 

Isolate

 

Isolate

(open)

 

(closed)

 

Process

 

Next, open the isolate valve on the low pressure side of the transmitter.

H

 

L

Drain/

 

Drain/

 

 

Vent

 

Vent

 

 

Valve

Equalize

Valve

 

 

 

 

(closed)

 

Isolate

 

Isolate

(open)

 

(open)

 

Process

 