Simulation

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

Other Types of Modes

Other types of modes are Cas, RCas, ROut, IMan and LO. Some of these may be supported by different function blocks in the Rosemount 2051. For more information, see the Function Block manual, document 00809-0100-4783.

NOTE

When an upstream block is set to OOS, this will impact the output status of all downstream blocks. The figure below depicts the hierarchy of blocks:

Simulation

 

Resource

 

 

Transducer

 

Analog Input

 

 

Other

 

 

Block

 

 

Block

 

(AI Block)

 

 

function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blocks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Simulation is the functionality of the AI block. To support testing, either change the mode of the block to manual and adjust the output value or enable simulation through the configuration tool and manually enter a value for the measurement value and its status (this single value will apply to all outputs). In both cases, first set the ENABLE jumper on the field device.

NOTE

All fieldbus instruments have a simulation jumper. As a safety measure, the jumper has to be reset every time there is a power interruption. This measure is to prevent devices that went through simulation in the staging process from being installed with simulation enabled.

With simulation enabled, the actual measurement value has no impact on the OUT value or the status. The OUT values will all have the same value as determined by the simulate value.

RESOURCE BLOCK

FEATURES and

FEATURES_SEL

The FEATURES parameter is read only and defines which features are supported by the 2051. Below is a list of the FEATURES the 2051 supports.

FEATURES_SEL is used to turn on any of the supported features that are found in the FEATURES parameter. The default setting of the Rosemount 2051 does not select any of these features. Choose one or more of the supported features if any.

UNICODE

All configurable string variables in the 2051, except tag names, are octet strings. Either ASCII or Unicode may be used. If the configuration device is generating Unicode octet strings, you must set the Unicode option bit.

REPORTS

The 2051 supports alert reports. The Reports option bit must be set in the features bit string to use this feature. If it is not set, the host must poll for alerts. If this bit is set, the transmitter will actively report alerts.

3-3