For each parameter n(n =1 - 4) displayed on the LCD there are several fields in the "Local Display" tab that must be setup.

Figure 3-5. Transducer500

Properties Local Display Screen

1.The first parameter is called "BLOCK TAG_n," here you must enter the exact name of the block to be displayed. This must be the same name as the one that is stored in the device.

2.Then select "BLOCK TYPE_n". This is a drop down menu showing the selections available in the device. Select the disired block to be displayed, in the "BLK_TYPE_n" field.

3.Select "UNITS_TYPE_n". Select "Custom" in this parameter if bringing a value from outside the Rosemount 2051 device. "Auto" has only pressure units, which might or might not match the disired selection.

4.The next parameter is called "CUSTOM_TAG_n.” This is an optional selection in identifying which parameter, block or device to be viewed on the LCD. This can be any name up to five characters long.

5.Then select "PARAM_INDEX_n". This is a drop down menu and the selections available in the device will appear. Select which parameter is to be displayed, in the "PARAM_INDEX_n" field.

6.Select "CUSTOM_UNITS_n” if "Custom" was selected previously in the "UNITS_TYPE_n" field above. This is limited to five characters and is where the disired units you wish to be displayed are entered.

7.To display more than one parameter be sure and check the appropriate number of boxes in the "Display Parameter Select" field.

3-12