Mount the Transmitter

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

Table 2-1. 2051L Dimensional Specifications

Except where indicated, dimensions are in inches (millimeters).

 

Pipe

Flange

Bolt Circle

Outside

No. of

Bolt Hole

Extension

O.D. Gasket

Class

Size

Thickness A

Diameter B

Diameter C

Bolts

Diameter

Diameter(1) D

Surface E

ASME B16.5 (ANSI) 150

2 (51)

0.69 (18)

4.75 (121)

6.0 (152)

4

0.75 (19)

NA

3.6 (92)

 

3 (76)

0.88 (22)

6.0 (152)

7.5 (191)

4

0.75 (19)

2.58 (66)

5.0 (127)

 

4 (102)

0.88 (22)

7.5 (191)

9.0 (229)

8

0.75 (19)

3.5 (89)

6.2 (158)

 

 

 

 

 

 

 

 

 

ASME B16.5 (ANSI) 300

2 (51)

0.82 (21)

5.0 (127)

6.5 (165)

8

0.75 (19)

NA

3.6 (92)

 

3 (76)

1.06 (27)

6.62 (168)

8.25 (210)

8

0.88 (22)

2.58 (66)

5.0 (127)

 

4 (102)

1.19 (30)

7.88 (200)

10.0 (254)

8

0.88 (22)

3.5 (89)

6.2 (158)

DIN 2501 PN 10–40

DN 50

20 mm

125 mm

165 mm

4

18 mm

NA

4.0 (102)

 

 

 

 

 

 

 

 

 

DIN 2501 PN 25/40

DN 80

24 mm

160 mm

200 mm

8

18 mm

65 mm

5.4 (138)

 

DN 100

24 mm

190 mm

235 mm

8

22 mm

89 mm

6.2 (158)

 

 

 

 

 

 

 

 

 

Mount the Transmitter

 

Pipe

Process

Lower Housing G

 

 

 

 

 

Class(1)

Size

Side F

1/4 NPT

1/2 NPT

H

ASME B16.5 (ANSI) 150

2 (51)

2.12 (54)

0.97 (25)

1.31 (33)

5.65 (143)

 

3 (76)

3.6 (91)

0.97 (25)

1.31 (33)

5.65 (143)

 

4 (102)

3.6 (91)

0.97 (25)

1.31 (33)

5.65 (143)

 

 

 

 

 

 

ASME B16.5 (ANSI) 300

2 (51)

2.12 (54)

0.97 (25)

1.31 (33)

5.65 (143)

 

3 (76)

3.6 (91)

0.97 (25)

1.31 (33)

5.65 (143)

 

4 (102)

3.6 (91)

0.97 (25)

1.31 (33)

5.65 (143)

DIN 2501 PN 10–40

DN 50

2.4 (61)

0.97 (25)

1.31 (33)

5.65 (143)

 

 

 

 

 

 

DIN 2501 PN 25/40

DN 80

3.6 (91)

0.97 (25)

1.31 (33)

5.65 (143)

 

DN 100

3.6 (91)

0.97 (25)

1.31 (33)

5.65 (143)

 

 

 

 

 

 

(1) Tolerances are -0.020 and +0.040 (-0,51 and +1,02)

Process Flange Orientation

Mount the process flanges with sufficient clearance for process connections. For safety reasons, place the drain/vent valves so the process fluid is directed away from possible human contact when the vents are used. In addition, consider the accessibility for a testing or calibration input.

NOTE

Most transmitters are calibrated in the horizontal position. Mounting the transmitter in any other position will shift the zero point to the equivalent amount of liquid head pressure caused by the varied mounting position. To reset zero point, refer to “Sensor Trim” on page 4-5.

Terminal Side of Electronics Housing

Mount the transmitter so the terminal side is accessible. Clearance of 0.75-in. (19 mm) is required for cover removal. Use a conduit plug on the unused side of the conduit opening.

Circuit Side of Electronics Housing

Provide 0.75 in. (19 mm) of clearance for units without an LCD display. Provide 3 in. (76 mm) of clearance for units installed with LCD.

Cover Installation

Always ensure a proper seal by installing the electronics housing covers so that metal contacts metal. Use Rosemount o-rings.

2-10