Wiring

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

Wiring

Wiring and power supply requirements can be dependent upon the approval

 

certification. As with all FOUNDATION fieldbus requirements, a conditioned

 

power supply and terminating resistors are required for proper operation. The

 

standard 2051 pressure transmitter terminal block is pictured in Figure 2-13.

 

The terminals are not polarity sensitive. The transmitter requires 9-32 Vdc to

 

operate. Type A FOUNDATION fieldbus wiring 18 awg twisted shielded pair is

 

recommended.

 

Avoid running instrument cable next to power cables in cable trays or near

 

heavy electrical equipment.

It is important that the instrument cable shield:

be trimmed close and insulated from touching the transmitter housing

be connected to the next shield if cable is routed through a junction box

be connected to a good earth ground at the power supply end

Figure 2-13. FOUNDATION fieldbus Wiring

Trim shield and insulate

DP

Insulate Shield

Connect Shield Back to the Power Supply Ground

Do not connect the power signal wiring to the test terminals. Voltage may burn out the reverse-polarity protection diode in the test connection.