Figure 5-2. Problems with communications flowchart

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

Figure 5-2. Problems with communications flowchart

COMMUNICATIONS ESTABLISHED BUT HAVE “BLOCK_ERR” OR AN “ALARM” CONDITION.

Read the following parameters in the Resource Block to determine the recommended action.

BLOCK_ERR (see Table 5-2)

SUMMARY_STATUS (see Table 5-3)

DETAILED_STATUS (see Table 5-4)

Problem Identified?

Yes

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If error condition does not exist in the Resource Block then it is a configuration problem, see “AI BLOCK_ERR Conditions.” in Table 5-8

Perform Recommended

 

 

 

 

For more detailed

Action, see Table 5-4.

 

information

 

 

 

 

 

 

 

 

 

 

 

 

Perform the following steps in the Sensor Transducer Block to determine the recommended action.

BLOCK_ERR (see Table 5-5)

XD_ERR (see Table 5-6)

DETAILED_STATUS (see Table 5-7)

RECOMMENDED_ACTION (see Table 5-7)

Problem Identified?

Yes

 

No

 

 

 

 

 

 

 

 

Perform Recommended

Action, see Table 5-9.

Problem Identified?

Yes

Perform Recommended Action, see Table 5-7.

No

If the problem persists contact your local Rosemount representative.

5-3