Block Errors

The table below lists conditions reported in the BLOCK_ERR parameter. Conditions in bold type are available. Conditions in italics are inactive for the Resource block and are given here only for your reference.

Condition

 

Number

Condition Name and Description

 

 

0

Other

1Block Configuration Error: A feature in FEATURES_SEL is set that is not supported by FEATURES or an execution cycle in CYCLE_SEL is set that

is not supported by CYCLE_TYPE.

3Simulate Active: This indicates that the simulation jumper is in place. This is not an indication that the I/O blocks are using simulated data.

4

Local Override

5

Device Fault State Set

 

 

6

Device Needs Maintenance Soon

7

Input failure/process variable has bad status

9Memory Failure: A memory failure has occurred in FLASH, RAM, or

EEROM memory

10Lost Static Data: Static data that is stored in non-volatile memory

has been lost.

11Lost NV Data: Non-volatile data that is stored in non-volatile memory

has been lost.

12

Readback Check Failed

 

 

13

Device Needs Maintenance Now

14

Power Up: The device was just powered-up.

 

 

15

Out of Service: The actual mode is out of service.

 

 