Long Term Stability

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

Long Term Stability

Models

Standard

Performance Option, P8

 

 

 

2051C(1)

 

 

Ranges 2-5

±0.1% of URL for 2 years

±0.125% of URL for 5 years

 

 

 

2051CD

 

 

Range 1

±0.2% of URL for 1 year

 

2051T(1)

 

 

Ranges 1-5

±0.1% of URL for 2 years

±0.125% of URL for 5 years

(1)Measured at reference conditions after exposure to temperature changes of up to ±50 °F (28 °C), and line pressure changes up to 1000 psi (6,9 mPa).

Dynamic Performance

4 - 20 mA HART(1)

 

1-5 Vdc HART Lower Power(1) Fieldbus(3)

Typical HART Transmitter Response Time

Total Response Time (Td + Tc)(2):

 

2051C, Range 3-5:

115 milliseconds

152 milliseconds

Range 1:

270 milliseconds

307 milliseconds

Range 2:

130 milliseconds

152 milliseconds

2051T:

100 milliseconds

152 milliseconds

2051L:

See Instrument Toolkit®

See Instrument Toolkit

Dead Time (Td)

60 milliseconds (nominal)

97 milliseconds

 

 

 

Update Rate

22 times per second

22 times per second

 

 

 

(1)Dead time and update rate apply to all models and ranges; analog output only

(2)Nominal total response time at 75 °F (24 °C) reference conditions.

(3)Transmitter fieldbus output only, segment macro-cycle not included.

Transmitter Output vs. Time

Pressure Released

 

 

Td

Tc

Td = Dead Time

Tc = Time Constant

100%

 

 

Response Time = Td+Tc

 

 

36.8%

 

63.2% of Total

 

Step Change

 

 

0%

Time

 

Line Pressure Effect per 1000 psi (6,9 MPa)

For line pressures above 2000 psi (13,7 MPa) and Ranges 4-5, see user manual (Rosemount publication number 00809-0100-4101).

Models

Line Pressure Effect

 

 

2051CD

Zero Error(1)

Ranges 2-3 ±0.1% of URL/1000 psi (68,9 bar) for line pressures from 0 to 2000 psi (0 to 13,7 MPa)

Range 1

±0.5% of URL/1000 psi (68,9 bar)

 

Span Error

Ranges 2-3

±0.1% of reading/1000 psi (68,9 bar)

Range 1

±0.4% of reading/1000 psi (68,9 bar)

(1) Can be calibrated out at line pressure.

A-2

Page 74
Image 74