Emerson Process Management 2051 manual Rosemount, Reference Manual, Simulate_STATE

Models: 2051

1 152
Download 152 pages 41.56 Kb
Page 140
Image 140
Simulate_STATE

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

 

Index

 

Parameter

Number

Description

 

 

 

Simulate_STATE

66

The state of the simulate jumper.

 

 

0 = Uninitialized

 

 

1 = Jumper/ switch off, simulation not allowed

 

 

2 = Jumper/ switch on, simulation not allowed (need to cycle jumper/ switch)

 

 

 

simulate_IO

64

Status of simulate jumper/switch.

RB_SFTWR_REV_ALL

51

The string will contain the following fields:

 

 

Major rev: 1-3 characters, decimal number 0-255

 

 

Minor rev: 1-3 characters, decimal number 0-255

 

 

Build rev: 1-5 characters, decimal number 0-255

 

 

Time of build: 8 characters, xx:xx:xx, military time

 

 

Day of week of build: 3 characters, Sun, Mon,...

 

 

Month of build: 3 characters, Jan, Feb...

 

 

Day of month of build: 1-2 characters, decimal number 1-31

 

 

Year of build: 4 characters, decimal

 

 

Builder: 7 characters, login name of builder

 

 

 

RB_SFTWR_REV_BUILD

50

Build of software that the resource block was created with.

RB_SFTWR_REV_MAJOR

48

Major revision of software that the resource block was created with.

 

 

 

RB_SFTWR_REV_MINIOR

49

Minor revision of software that the resource block was created with.

start_with_defaults

63

0 = Uninitialized

 

 

1 = do not power-up with NV defaults

 

 

2 = power-up with default node address

 

 

3 = power-up with default pd_tag and node address

 

 

4 = power-up with default data for the entire communications stack (no application data)

 

 

 

STRATEGY

03

The strategy field can be used to identify grouping of blocks.

ST_REV

01

The revision level of the static data associated with the function block.

 

 

 

summary_status

56

An enumerated value of repair analysis.

TAG_DESC

02

The user description of the intended application of the block.

 

 

 

TEST_RW

08

Read/write test parameter - used only for conformance testing.

UPDATE_EVT

35

This alert is generated by any change to the static data.

 

 

 

WRITE_ALM

40

This alert is generated if the write lock parameter is cleared.

WRITE_LOCK

34

If set, no writes from anywhere are allowed, except to clear WRITE_LOCK. Block inputs

 

 

will continue to be updated.

 

 

 

WRITE_PRI

39

Priority of the alarm generated by clearing the write lock.

 

 

 

C-10

Page 140
Image 140
Emerson Process Management 2051 manual Rosemount, Reference Manual, Simulate_STATE