Load Limitations

Maximum loop resistance is determined by the voltage level of the external power supply, as described by:

Table A-1.

Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)

Load (Ohms)

1387

1000

500Operating

Region

0 Manual background

10.5 20 30

Voltage (V dc)

42.4

 

The HART communicator requires a minimum loop resistance of 250Ω for communication.

FOUNDATIONfieldbus (Output Code F)

Power Supply

External power supply required; transmitters operate on 9.0 to 32.0 V dc transmitter terminal voltage.

Current Draw

17.5 mA for all configurations (including LCD display option)

Turn-On Time

Performance within specifications less than 20.0 sections after power is applied to the transmitter.

FOUNDATION fieldbus Function Block Execution Times

 

Block

Execution Time

 

 

 

 

Resource

-

 

 

 

 

Transducer

-

 

LCD Block

-

 

 

 

 

Analog Input 1, 2

30 milliseconds

 

PID

45 milliseconds

 

FOUNDATION fieldbus Parameters

 

 

Schedule Entries

7 (max.)

 

 

 

 

Links

20 (max.)

 

Virtual Communications Relationships

12 (max.)

 

(VCR)

 

Standard Function Blocks

Resource Block

Contains hardware, electronics, and diagnostic information.

Transducer Block

Contains actual sensor measurement data including the sensor diagnostics and the ability to trim the pressure sensor or recall factory defaults.

A-5