Delta Electronics manual CANopen Communication Module DVPCOPM-SL

Models: DVPCOPM-SL

1 32
Download 32 pages 6.11 Kb
Page 31
Image 31
Manual background

CANopen Communication Module DVPCOPM-SL

Code

Indication

How to correct

F9

Low voltage is deteced.

Check and make sure the power of

DVPCOPM-SL works normally.

 

 

FA

The firmware of DVPCOPM-SL is

Re-power DVPCOPM-SL.

in error status.

 

 

FB

The sending buffer in

Make sure the bus works normally and re-power

DVPCOPM-SL is full.

DVPCOPM-SL.

 

FC

The receiving buffer in

Make sure the bus works normally and re-power

DVPCOPM-SL is full.

DVPCOPM-SL.

 

E0

DVPCOPM-SL receives

Read relevant information through PLC MPU or

Emergency message sent by the

Delta CANopenBuilder software.

 

slave.

 

 

 

 

 

E1

PDO data length returned from the

Reset the PDO data length in the slave and

slave is not consistent with the

download the new setting to DVPCOPM-SL.

 

length set in the node list.

 

 

 

 

 

E2

PDO message from the slave has

Check and make sure the setting is correct.

not been received.

 

 

E3

Auto SDO download failed.

Check and make sure auto SDO is correct.

 

 

 

E4

PDO parameter setting has failed.

Make sure the PDO parameter setting is legal.

 

 

 

E5

Error in key parameter setting.

Make sure all the slaves connected are

consistentwith the slaves set.

 

 

E6

The slave does not exist in the

 

network.

Make sure the power of the slave and the

 

E7

The slave's error control is

network connection work normally.

timed-out.

 

 

 

E8

Master/slave node address is

Reset the node address and make sure the new

repeated.

address is not a repeated one.

 

zDVPCOPM-SL as slave:

Code

Indication

How to correct

0 ~ 7F

The node address of DVPCOPM-SL

--

 

when in normal operation.

 

A0

The parameters in DVPCOPM-SL is

--

 

being initialized.

 

A1

DVPCOPM-SL is in pre-operational

--

status.

 

 

A3

The data are being downloaded to

--

DVPCOPM-SL.

 

 

B0

Heartbeat timed-out

Re-connect DVPCOPM-SL to the network.

 

 

 

B1

PDO data length returned from the

Reset the PDO data length in the slave and

slave is not consistent with the

download the new setting to DVPCOPM-SL.

 

length set in the node list.

 

 

 

 

 

F4

Bus-off is detected

Make sure the communication cable is in normal

operation, and all the nodes on the network work

 

 

in the same baud rate. Re-power DVPCOPM-SL.

FB

The sending buffer in

Make sure the bus works normally and re-power

DVPCOPM-SL is full.

DVPCOPM-SL.

 

FC

The receiving buffer in

Make sure the bus works normally and re-power

DVPCOPM-SL is full.

DVPCOPM-SL.

 

DVP-PLC Application Manual

29

Page 31
Image 31
Delta Electronics manual CANopen Communication Module DVPCOPM-SL