INSTALLATION (continued)
CHART 1 (Figures 20 and 21)
Venting with One (1) 90° Elbow or Two (2) 90° Elbows
Total Vertical | Total Horizontal |
(With Fire Box) V | H1 or H1 + H2 |
4.5' minimum | 3' maximum |
|
|
4.5' minimum | 4' maximum |
|
|
5' minimum | 8' maximum |
|
|
6' minimum | 12' maximum |
|
|
7' minimum | 15' maximum |
|
|
8' minimum | 20' maximum |
|
|
25' maximum vertical |
|
20' maximum horizontal run |
|
Figure 21 and Chart 1 list examples of possible venting systems using two (2) 90° elbows. V is listed as minimum vertical dimensions and H1 + H2 is listed as total of maximum horizontal dimensions. The maximum vertical and horizontal distances for two (2) 90° elbows as shown in Figure 21 are 20 feet.
Attention: Refer to Figure 10 for additional venting requirements.
10 3/8"
37 | 5/8" | ( 956mm) | ||||
|
| ELBOW | ||||
DVS | OF | |||||
CENTER |
| OUT | ||||
STRAIGHT | ||||||
|
|
|
Figure 22
12 3/8"
| 36 | 44 | 3/4" | 114cm | |||
| 118cm | ||||||
|
|
|
| ||||
- |
|
|
|
|
| ||
DVS | 46 | 3/4" |
| ||||
|
| ||||||
|
| ELBOW | |||||
DVS |
| OF | |||||
CENTER |
|
| |||||
|
| OUT | |||||
STRAIGHT |
|
|
SEE CHART FOR PERMISSIBLE "H" AND "V" DIMENSIONS
NOTE: H1 AND H2 MUST BE ADDED TOGETHER TO USE CHART
Figure 21
Figure 23
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent termination will be centered (if possible) between two (2) studs. This will avoid any extra framing. All vent kit pipes should be assembled on the unit after the unit is moved into the final position.