CONFIGURING THE CARD
EATON PowerXpert®Gateway Series 1000 Card User’s Guide S164201670 Rev 1
24
Management from an SNMP NMS
To access the PXGX Series 1000 Card via SNMP:
1. Use these default Community strings:
GET Community string: public
SET Community string: private
2. From the card’s Web page, click the Documentation link from the
menu bar (or visit www.eaton.com/powerxpert) for the following
MIB files for the PXGX Series 1000 Card:
MIBName Filename Description
EatonPDU MIB EATON-PDU-MIB.txt Metersavailable from the PDU, including
identification,input, output, configuration,
tests,alarms, bypass, traps, panel data, and
circuitbreaker data
EatonEMP MIB EATON-EMP-MIB.txt Metersand settings for the EMP
EatonAlarms+Traps MIB EATON-PXG-MIB.txt Alarmsand notifications (traps)
EatonObject Identifier (OID)
assignments
EATON-OIDS.txt Basedocument for all OID assignmentsfor
EatonsMIBs
RFC4133 Entity MIB ENTITY-MIB.txt Identificationand description of each device
attachedto the card
RFC4268 Entity State MIB ENTITY-STATE-MIB.txt Fiveavailability status meters for each
deviceattached to the card
RFC4268 Entity State MIB, part 2 ENTITY-STATE-TC-MIB.txt Possible state values for the Entity State MIB
Add these files to the MIB database of your SNMP management
software (such as HP OpenViewtIBMRDirector, and Sun
NetManager).
3. Use the facilities provided by the SNMP management software to
access the individual MIB objects. See Chapter 4, “MIB Files,” on
page 45 for more information.
,