MODBUS REGISTERS
EATON PowerXpert®Gateway Series 1000 Card User’s Guide S164201670 Rev 1 65
Table7. Breaker #1 Data Registers (FC04) (continued)
BytesData TypeRegisterName
ACMAX Current Phase C 1047 FLOAT 4
PercentFL Current A 1049 FLOAT 4
PercentFL Current B 1051 FLOAT 4
PercentFL Current C 1053 FLOAT 4
WattsPhase A 1055 FLOAT 4
WattsPhase B 1057 FLOAT 4
WattsPhase C 1059 FLOAT 4
WattsPhase A MAX 1061 FLOAT 4
WattsPhase B MAX 1063 FLOAT 4
WattsPhase C MAX 1065 FLOAT 4
VAPhase A 1067 FLOAT 4
VAPhase B 1069 FLOAT 4
VAPhase C 1071 FLOAT 4
VAPhase A MAX 1073 FLOAT 4
VAPhase B MAX 1075 FLOAT 4
VAPhase C MAX 1077 FLOAT 4
PFDisplacement Phase A 1079 FLOAT 4
PFDisplacement Phase B 1081 FLOAT 4
PFDisplacement Phase C 1083 FLOAT 4
PFDisplacement A Minimum 1085 FLOAT 4
PFDisplacement B Minimum 1087 FLOAT 4
PFDisplacement C Minimum 1089 FLOAT 4
PFDisplacement A Maximum 1091 FLOAT 4
PFDisplacement A Maximum 1093 FLOAT 4
PFDisplacement A Maximum 1095 FLOAT 4
kWHours 1097 FLOAT 4
kWHours Monthly 1099 FLOAT 4
kWHours Yearly 1101 FLOAT 4