MODBUS REGISTERS
EATON PowerXpert®Gateway Series 1000 Card User’s Guide S164201670 Rev 1
68
Environmental Monitoring Probe (FC 03 or 04)The optional Environmental Monitoring Probe for the PDU/RPP can
measure temperature and humidity. Because the device can be located
outside the PDU/RPP, the reference is to “auxiliary” data. In addition, it
contains two connections for monitoring the condition of auxiliary input
contacts, such as a door switch. See Table 9 for a list of EMP registers.
An exception code is returned if the EMP is not installed.
To read the temperature at the PDU/RPP, set the Modbus program to
Unit ID 254 and coil address 12028:
IP: <IP address of PDU/RPP>
Unit ID: 254
Starting Register: 12028
Number of registers: 2
Function Code: 04
Table9. Environmental Monitor (FC 03 or 04)
Name Register DataType Bytes
VendorName 1001 STRING 64
ModelName 1033 STRING 64
DisplayName 1065 STRING 64
SerialNumber 1123 STRING 64
DeviceID 1099 UINT 4
AuxiliaryInput 1 10275 UINT 2
AuxiliaryInput 2 10276 UINT 2
AuxiliaryTemperature 12028 FLOAT 4
AuxiliaryHumidity 12030 FLOAT 4