MODBUS REGISTERS
EATON PowerXpert®Gateway Series 1000 Card User’s Guide S164201670 Rev 1
56
Table3. PDU/RPP Registers (FC04) (continued)
BytesDataTypeRegisterName
ACV ratio C out 4164 FLOAT 4
ACI Gnd 5008 FLOAT 4
ACI in A 5022 FLOAT 4
ACI in B 5024 FLOAT 4
ACI in C 5026 FLOAT 4
ACI out A 5028 FLOAT 4
ACI out B 5030 FLOAT 4
ACI out C 5032 FLOAT 4
ACI out N 5034 FLOAT 4
ACI out A Limit 5038 FLOAT 4
ACI out B Limit 5040 FLOAT 4
ACI out C Limit 5042 FLOAT 4
ACI ratio A in 5094 FLOAT 4
ACI ratio B in 5096 FLOAT 4
ACI ratio C in 5098 FLOAT 4
ACI ratio A out 5100 FLOAT 4
ACI ratio B out 5102 FLOAT 4
ACI ratio C out 5104 FLOAT 4
Wattsin Total 6022 FLOAT 4
Wattsout Total 6024 FLOAT 4
VAin Total 6086 FLOAT 4
VAout Total 6088 FLOAT 4
PFDisp out 6202 FLOAT 4
PFDisp in 6204 FLOAT 4
OutputkW Hours 7002 FLOAT 4
IA in THD 8008 FLOAT 4
IB in THD 8010 FLOAT 4
IC in THD 8012 FLOAT 4