MODBUS REGISTERS
EATON PowerXpert®Gateway Series 1000 Card User’s Guide S164201670 Rev 1
58
Table4. PDU/RPP Alarms (FC02)Name Register DataType
ACInput Over Volts 1006 BOOL
ACInput Under Volts 1007 BOOL
InputFrequency Fault 1008 BOOL
ACOutput Over Volts 1009 BOOL
ACOutput Under Volts 1010 BOOL
ACOutput Frequency Fault 1011 BOOL
RemoteEPO 1012 BOOL
BuildingAlarm 4 1016 BOOL
BuildingAlarm 3 1017 BOOL
BuildingAlarm 2 1018 BOOL
BuildingAlarm 1 1019 BOOL
OutputOverload 1025 BOOL
SystemBus Overload 1050 BOOL
NVMemory Failure 1053 BOOL
InternalComm Failure 1062 BOOL
InputPhase Rotation 1089 BOOL
EmergencyShutdown 1093 BOOL
OverloadA 1139 BOOL
OverloadB 1140 BOOL
OverloadC 1141 BOOL
OverloadHigh Phase A 1142 BOOL
OverloadHigh Phase B 1143 BOOL
OverloadHigh Phase C 1144 BOOL
OverloadExtreme Phase A 1145 BOOL
OverloadExtreme Phase B 1146 BOOL
OverloadExtreme Phase C 1147 BOOL
XformerOver Temperature 1164 BOOL
CheckModem 1174 BOOL
ConfigurationError 1182 BOOL
SystemNotice Active 1185 BOOL