POST ASSEMBLY TESTS

Reference Manual

00809-0100-4514, Rev BA January 2008

Rosemount 1154

POST ASSEMBLY TESTS

1.Conduct hydrostatic testing to 150% of maximum working pressure or 2,000 psi, whichever is greater.

2.Calibrate the transmitter per the calibration section of this manual.

3.Conduct nuclear cleaning to 1 ppm chloride content of transmitter “wetted parts.”

Table 5-2. Torque References.

ITEM(S) TO BE TORQUED

TORQUE VALUE

TOLERANCE

 

 

 

Bracket to Mounting Panel Bolts

19 ft-lb (26 N-m)

±1 ft-lb (1 N-m)

 

 

 

Transmitter to Bracket Bolts

21 ft-lb (29 N-m)

±1 ft-lb (1 N-m)

 

 

 

Swagelok Process Fittings

See Installation Instructions

 

 

 

Drain/Vent Valves

7.5 ft-lb (10 N-m)

±0.5 ft-lb (0.7 N-m)

 

 

 

Covers

16.5 ft-lb (22.4 N-m)

±1 ft-lb (1 N-m)

 

 

 

Module Neck Lock Nut

35 ft-lb (48 N-m)

±1 ft-lb (1 N-m)

 

 

 

Conduit Fitting

4 to 7 turns or a minimum of 12.5 ft-lb (16.9

±1 ft-lb (1 N-m)

 

N-m)

 

 

 

 

Flange Bolts

See Process Flange Reassembly

 

 

 

Terminal Block Screws

5 in-lb (0.6 N-m) or hand tight

±1 in-lb (0.1 N-m)

 

 

 

Amplifier Board Screws

Nominal 10 in-lb (1.1 N-m)

 

 

 

Table 5-3. Troubleshooting.

Symptom

Potential Source

Corrective Action

 

 

 

High Output

Primary Element

Check for restrictions at primary element, improper installation or poor condition. Note any

 

 

changes in process fluid properties that may affect output.

 

 

 

 

Impulse Piping

Check for leaks or blockage.

 

 

Ensure blocking locking valves are fully open.

 

 

Check for entrapped gas in liquid lines, or liquid in dry lines.

 

 

Ensure that density of fluid in impulse line is unchanged.

 

 

Check for sediment in transmitter process flanges.

 

 

 

 

Transmitter

Make sure that post connectors and the sensor connections are clean. If the electronics are

 

Electronics

still suspect, substitute new electronics.

 

 

 

 

Transmitter

Determine faulty circuit board by trying spare boards. Replace faulty circuit board.

 

Electronics Failure

 

 

 

 

 

Sensing Module

See Sensing Module Checkout section. The sensing element is not field repairable and must

 

 

be replaced if found to be defective. See “Disassembly Procedure” for instructions on

 

 

disassembly. Check for obvious defects, such as a punctured isolating diaphragm or fill fluid

 

 

loss, and contact Rosemount Nuclear Instruments, Inc. at (952) 949-5210.

 

 

 

 

Power Supply

Check the power supply output voltage at the transmitter.

 

 

 

 

 

Continued on Next Page

 

 

 

 

 

 

5-9

Page 43
Image 43