Rosemount 1154

Reference Manual

00809-0100-4514, Rev BA January 2008

Symptom

Potential Source

Corrective Action

 

 

 

Low Output or

Primary Element

Check for restrictions at primary element, improper installation or poor condition.

No Output

 

Note any changes in process fluid properties that may affect output.

 

 

 

 

Loop Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not use over 100 volts to check the loop, or damage to the transmitter

 

 

 

electronics may result.

 

 

 

 

 

 

 

 

Check for adequate voltage to the transmitter.

 

 

Check the milliamp rating of the power supply against the total current being drawn for all

 

 

transmitters being powered.

 

 

Check for shorts and multiple grounds.

 

 

Check for proper polarity at the signal terminal.

 

 

Check loop impedance.

 

 

Check wire insulation to detect possible shorts to ground.

 

 

 

 

 

 

Impulse Piping

Ensure that the pressure connection is correct.

 

 

Check for leaks or blockage.

 

 

Check for entrapped gas in liquid lines.

 

 

Check for sediment in the transmitter process flange.

 

 

Ensure that blocking valves are fully open and that bypass valves are tightly closed.

 

 

Ensure that density of the fluid in the impulse piping is unchanged.

 

 

 

 

 

 

Transmitter

Ensure that calibration adjustments are in allowable range.

 

Electronics

Check for shorts in sensor leads.

 

Connections

Make sure post connectors are clean, and check the sensor connections.

 

 

If the electronics are still suspect, substitute new electronics.

 

 

 

 

 

 

Test Diode Failure

Replace electronics housing.

 

 

 

 

 

 

Transmitter

Determine faulty circuit board by trying spare boards. Replace faulty circuit board.

 

Electronics Failure

 

 

 

 

 

 

 

 

 

Sensing Module

NOTE: See Sensing Module Checkout section. The sensing element is not field repairable

 

 

and must be replaced if found to be defective. See “Disassembly Procedure” for instructions

 

 

on disassembly. Check for obvious defects, such as a punctured isolating diaphragm or fill

 

 

fluid loss, and contact Rosemount Nuclear Instruments, Inc. at (952) 949-5210.

 

 

 

 

 

 

Power Supply

Check the power supply output voltage at the transmitter.

 

 

 

 

 

Erratic Output

Loop Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not use over 100 volts to check the loop, or damage to the transmitter

 

electronics may result.

 

 

 

 

Check for inadequate voltage to the transmitter.

 

Check for intermittent shorts, open circuits, or multiple grounds.

 

 

 

Impulse Piping and

Check for entrapped gas in liquid lines, or liquid in dry lines.

Process

 

 

Connections

 

 

 

 

 

Transmitter

Check for intermittent shorts or open circuits.

Electronics

Make sure that bayonet and sensor connectors are clean and properly connected.

 

 

 

Transmitter

Determine faulty circuit boards by trying spare boards. Replace faulty circuit board.

Electronics Failure

 

 

 

 

 

Power Supply

Check power supply output voltage.