Post DBE Operation

Accuracy at reference conditions shall be within ±2.5% of upper range limit (±3.75% for Range Code 0) for one year following DBE.

Quality Assurance Program

In accordance with NQA-1, 10CFR50 Appendix B, and ISO 9001:2000

Nuclear Cleaning

To 1 ppm maximum chloride content

Hydrostatic Testing

To 150% of maximum working pressure or 2,000 psi (13.8 MPA), whichever is greater

Traceability

In accordance with NQA-1, 10CFR50 Appendix B; chemical and physical material certification of pressure-retaining parts

Qualified Life

The transmitter qualified life is dependent on continuous ambient temperature at the installation site (see Figure 6-1). Replacement of amplifier and calibration circuit boards at the end of their qualified life permits extension of the transmitter qualified life to the module qualified life. See Rosemount Report D8400102 for details.

Figure 6-1. Qualified Life vs. Ambient Temperature.

Module

Qualified Life

Electronics

Qualified Life

Time (Years)

Temperature (°F)

PERFORMANCE SPECIFICATIONS

Based on zero-based ranges under reference conditions.

Accuracy

±0.25% of calibrated span; includes combined effects of linearity, hysteresis, and repeatability

Dead Band

None