Table 27 Parallel system current table

Specifications and Technical Data

11.2Cable Lengths: Floor to Connection Point Inside UPS

To help calculate the total cable length required, refer to Table 26 for the distance from the floor to selected connection points inside the Liebert NX. Determine the cable length required to reach the Liebert NX, then add the appropriate length from the table and adequate slack for repair and mainte- nance.

Table 26 Distance to connection points on the Liebert NX UPS

 

Distance

 

 

 

 

From Floor

From Top of Unit

Connection Point on UPS

in. (mm)

in. (mm)

Bypass AC input supply

13 (330)

66 (1676)

 

 

 

UPS output AC

13 (330)

66 (1676)

 

 

 

Battery power

13 (330)

66 (1676)

 

 

 

Auxiliary cables: Monitor board (U2)

67 (1702)

11 (279)

 

 

 

Liebert IntelliSlot Communications

60 (1524)

19 (483)

 

 

 

Ground

13 (330)

66 (1676)

 

 

 

Parallel Board

70 (1780)

11 (279)

 

 

 

Table 27 Parallel system current table

 

 

 

System I/P

 

System

 

Nominal

Output

System

 

 

Voltage

System Max

Input OCPCB

O/P Voltage

O/P Current

OCPCB

Size

Type

kVA

(VAC)

Input Current

Size (A)

(VAC)

Rating (A)

Size (A)

 

E

80

480V

135.0

200

480V

96.2

125

 

 

 

 

 

 

 

 

 

120

480V

202.5

300

480V

144.3

200

 

 

 

 

 

 

 

 

 

 

 

1+1

E1

80

480V

135.0

200

480V

96.2

125

 

 

 

 

 

 

 

120

480V

202.5

300

480V

144.3

200

 

 

 

 

 

 

 

 

 

 

 

 

E2

80

N/A

N/A

N/A

480V

96.2

125

 

 

 

 

 

 

 

 

 

120

N/A

N/A

N/A

480V

144.3

200

 

 

 

 

 

 

 

 

 

 

 

 

E

80

480V

270.0

350

480V

192.5

250

 

 

 

 

 

 

 

 

 

120

480V

405.0

600

480V

288.7

400

 

 

 

 

 

 

 

 

 

 

 

2+1

E1

80

480V

270.0

350

480V

192.5

250

 

 

 

 

 

 

 

120

480V

405.0

600

480V

288.7

400

 

 

 

 

 

 

 

 

 

 

 

 

E2

80

N/A

N/A

N/A

480V

192.5

250

 

 

 

 

 

 

 

 

 

120

N/A

N/A

N/A

480V

288.7

400

 

 

 

 

 

 

 

 

 

 

 

 

E

80

480V

405.0

600

480V

288.7

400

 

 

 

 

 

 

 

 

 

120

480V

607.5

800

480V

433.0

600

 

 

 

 

 

 

 

 

 

 

 

3+1

E1

80

480V

405.0

600

480V

288.7

400

 

 

 

 

 

 

 

120

480V

607.5

800

480V

433.0

600

 

 

 

 

 

 

 

 

 

 

 

 

E2

80

N/A

N/A

N/A

480V

288.7

400

 

 

 

 

 

 

 

 

 

120

N/A

N/A

N/A

480V

433.0

600

 

 

 

 

 

 

 

 

 

 

 

Type E: BB0, FB0 and KB0 configurations

Type E1: CB1, GB1, LB1 configurations;

Type E2: CB2, CB3, CB4 configurations

Use wiring rated at 75°C or greater.

92

Page 100
Image 100
Emerson 60HZ, 480V user manual Parallel system current table, Specifications and Technical Data

60HZ, 480V specifications

The Emerson 40-120KVA UPS is a high-performing uninterruptible power supply designed to ensure the reliability and continuity of critical operations across various industries. This UPS operates at 480VAC and 60Hz, making it suitable for environments where high-power demands are common.

One of the standout features of this UPS system is its modular design, which allows for easy scalability. Organizations can expand their power capacity as their needs grow, making the Emerson 40-120KVA UPS a future-proof investment. The system operates with high efficiency, minimizing energy consumption and operational costs. This is vital for data centers and industrial applications where energy management is increasingly important.

The Emerson UPS incorporates advanced digital signal processing technology, delivering real-time monitoring and control. This enhances the overall performance and reliability of the system, providing seamless power protection against voltage fluctuations, surges, and interruptions. With a total harmonic distortion of less than 5%, the UPS ensures a clean and stable power output, preserving the integrity of sensitive electronic equipment.

Another noteworthy characteristic of the Emerson 40-120KVA is its redundancy features. The system supports N+1 redundancy, allowing for one extra module to ensure uninterrupted service in case of a failure. This design offers peace of mind for critical applications, ensuring that there is no single point of failure.

User-friendliness is also a significant aspect of the Emerson UPS. The intuitive graphical user interface simplifies monitoring and management, allowing operators to assess system performance and status at a glance. Additionally, remote monitoring capabilities enable real-time tracking of system health and performance from anywhere, providing flexibility and oversight for facility managers.

The Emerson 40-120KVA UPS also meets stringent safety and compliance standards, ensuring reliable operation in demanding environments. Its robust design is suitable for a variety of applications, including information technology, telecommunications, and industrial processes. Overall, the Emerson 40-120KVA UPS stands out as a reliable, efficient, and versatile solution for businesses aiming to safeguard their critical power supply against any disruption.