Emerson 480V, 60HZ user manual •Close CB5 CB1, CB2, CB3 and CB5 are closed

Models: 60HZ 480V

1 112
Download 112 pages 61.01 Kb
Page 87
Image 87
•Close CB5 (CB1, CB2, CB3 and CB5 are closed).

Operating Instructions

After initialization, the bypass SCR closes. Because the output circuit breaker is still open, the UPS channels power through the Maintenance Bypass Supply line (CB3). The bypass indicator extinguishes, provided that the bypass is normal.

The opening display is shown in the figure at right. The UPS Mimic display indicators will be:

Indicator

State

 

 

Rectifier indicator

Green

 

 

Battery indicator

Red

 

 

Bypass indicator

Off

 

 

Inverter indicator

Off

 

 

Output indicator

Off

 

 

Status indicator

Off

 

 

F1

F2

F3

F4

HELP

Close CB5 (CB1, CB2, CB3 and CB5 are closed).

The Maintenance Bypass supply is now in parallel with the UPS Static Switch supply.

Verify that the Bypass indicator is Green, then open CB3.

The UPS powers from static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The design of the hardware and software ensures uninterrupted output.

3.Close external battery circuit breaker.

After the UPS detects that the battery is connected, the red battery indicator extinguishes moments after the battery charger starts operation.

The UPS Mimic display indicators will be

Indicator

State

 

 

Rectifier indicator

Green

 

 

Battery indicator

Off

 

 

Bypass indicator

Green

 

 

Inverter indicator

Off

 

 

Output indicator

Green

 

 

Status indicator

Amber

 

 

4.Press the INVERTER ON control button for 2 seconds.

The inverter will start and the inverter indicator will flash green. After the inverter is ready, the

UPS will transfer from bypass to inverter, the bypass indicator will turn off and the inverter and load indicators will turn on.

The UPS is operating normally. The UPS Mimic display indicators will:

Indicator

State

Rectifier indicator

Green

 

 

Battery indicator

Off

 

 

Bypass indicator

Off

 

 

Inverter indicator

Green

 

 

Output indicator

Green

 

 

Status indicator

Green

 

 

79