Installation Drawings

6.0INSTALLATION DRAWINGS

The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert NX UPS System cabinets.

Figure 21 Liebert NX 40-120kVA dimensional view—front and left side

Center of Gravity

600mm

Without Internal Battery

 

 

 

(23.6")

 

 

997mm

(39.3")

39.6mm Front 360mm

(1.6") (14.2")

Left Side

2000mm

 

(78.7")

 

301mm

 

(11.9")

Front

 

Liquid

Crystal

Display

1.All dimensions are in millimeters (in.).

2.Eight-inch minimum clearance above unit required for air exhaust.

3.Keep cabinet within 15 degrees of vertical while handling.

4.Top and bottom cable entry available through removable access plates. Remove access plate, punch to suit conduit size and replace.

5.Color - black.

6.Unit bottom is structurally adequate for forklift handling.

7.Open door to replace air filter, washable type.

8.M10 threaded mounting holes used for seismic anchoring or floor stand.

NOTE: If floor stand is used, the weight of the unit must be supported under all casters.

9.Each mounting location is supported by (2) 10ga. (.135") galvanized steel. The threaded insert is approximately 3/4" deep. Mounting holes are underneath unit base; mounting bolts must be threaded into unit.

10.Includes side panel. Side panels must be removed from adjacent units that are bolted together.

11.Leveling feet are not designed to carry the full weight of the cabinet.

12.Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.