5.4UPS Electrical Characteristics

UPS Specifications

5.4UPS Electrical Characteristics

Table 8 UPS terminal

Input (For Single-Input Unit)

 

 

 

 

 

 

Maximum Recommended Lug

 

Nominal

Maximum

 

OCP

 

(Thomas & Betts Part #)

 

 

 

 

 

Unit

Input

Input

OCP

Device

Bolt

Compression

Mechanical

Rating

Current

Current

Current

Rating

Size

2-Hole; 3/8" Bolt

2-Hole;

40

48

66.8

80.2

90

M8

54106

ADR21

60

72

100.2

120.3

125

M8

54108

ADR21

80

96

133.6

160.4

175

M8

54157

ADR21

100

120

167.1

200.5

225

M8

54167

ADR50

120

144

200.5

240.6

250

M8

54172-TB

ADR50

140

168

236

278

300

M10

54212

ADR50

160

192

270

318

350

M10

54213

ADR50

200

240

337

397

400

M10

54209

ADR80

Rectifier

Input (For Dual Input Unit Only)

 

 

 

 

 

 

 

 

 

 

 

Maximum Recommended Lug

 

Nominal

Maximum

 

OCP

 

(Thomas & Betts Part #)

Unit

Input

Input

OCP

Device

Bolt

Compression

Mechanical

Rating

Current

Current

Current

Rating

Size

2-Hole; 3/8" Bolt

2-Hole

40

48

67.5

83

90

M8

54106

ADR21

60

72

101.3

124.5

125

M8

54108

ADR21

80

96

135

166

175

M8

54157

ADR21

100

120

168.8

207.6

225

M8

54167

ADR50

120

144

202.5

249.1

250

M8

54172-TB

ADR50

140

168

236

278

300

M10

54212

ADR50

160

192

270

318

350

M10

54213

ADR50

200

240

337

397

400

M10

54209

ADR80

Bypass Input (For Dual Input Units)

 

 

 

 

 

 

 

 

 

 

Maximum Recommended Lug

 

 

 

 

 

 

(Thomas & Betts Part #)

 

Unit

Nominal

Maximum

OCP

Bolt

Compression

Mechanical

 

Input

Input

Device

2-Hole; 3/8"

 

Rating

Current

Current

Rating

Size

Bolt

2-Hole

 

40

48

66.8

70

M8

54106

ADR21

 

60

72

100.2

110

M8

54107

ADR21

 

80

96

133.6

150

M8

54152-TB

ADR21

 

100

120

167.1

175

M8

54157

ADR21

 

120

144

200.5

225

M8

54167

ADR50

 

140

168

233

300

M10

54212

ADR50

 

160

192

268

350

M10

54213

ADR50

 

200

240

334

400

M10

54209

ADR50

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Recommended Lug

 

 

 

 

 

 

(Thomas & Betts Part #)

 

Unit

Nominal

Maximum

OCP

Bolt

Compression

Mechanical

 

Output

Output

Device

2-Hole; 3/8"

 

Rating

Current

Current

Rating

Size

Bolt

2-Hole

 

40

48

66.8

70

M8

54106

ADR21

 

60

72

100.2

110

M8

54107

ADR21

 

80

96

133.6

150

M8

54152-TB

ADR21

 

100

120

167.1

175

M8

54157

ADR21

 

120

144

200.5

225

M8

54167

ADR50

 

140

168

233

300

M10

54167

ADR50

 

160

192

268

350

M10

54172-TB

ADR50

 

200

240

334

400

M10

54209

ADR50

 