Emerson 480V, 60HZ Mimic display indicators location, Bypass indicator, Load indicator, Buzzer

Models: 60HZ 480V

1 112
Download 112 pages 61.01 Kb
Page 73
Image 73
Figure 47 Mimic display indicators location

Operator Control and Display Panel

8.2Mimic Display Indicators

The Mimic display on the front panel consists of six indicators arranged in a single-line diagram depicting the various paths of UPS power, as shown in Figure 47.

Figure 47 Mimic display indicators location

Bypass indicator

Load indicator

Inverter indicator

Rectifier indicator

LED1

 

LED2

LED4 LED5

Battery indicator

LED3

Buzzer

STATUS

 

Status indicator

 

Liebert NX

2007-01-06

09:20:37

80kVA-3X3

Single

 

Normal

 

Main

Bypass

Output

L-N current (A)

L1-N/L 2

L 2-N/L3

L 3-N/L1

71.4

70.8

71.3

Frequency (HZ)

59.9

59.9

59.9

L-L voltage (V)

480

480

480

PowerFactor

0. 99

0. 99

0.99

Input disconnect closed

01-06 09:15

Output disconnect closed

01-06 09:15

Bypass abnormal

01-06 09 :15

 

 

 

 

?

F1

F2

F3

F4

HELP

EPO

INVER TER OFF

FAULT CLEAR

SILENC E ON/OFF

INVERTER ON

The current operational status of the Liebert NX is indicated by the color of the indicators—green, amber or red—and whether they are ON (solid), flashing or OFF. Table 15 provides a guide to inter- preting the various states of the indicators.

Table 15 Mimic display status indicators

Indicator

 

 

 

 

(see

 

 

 

 

Figure 47)

Green

Flashing Green / Amber

Red

Off

Rectifier

Load on rectifier

Flashing Green: Utility normal,

Rectifier fault

Rectifier is normal, but utility is

 

but rectifier not operating

 

abnormal

 

 

 

 

Battery powering

Flashing Green: Battery pre-

Battery or battery

Battery and converter are

Battery

the load

warning (low battery)

converter abnormal*

normal, and battery is not

 

 

 

 

discharging

Inverter

Inverter powering

Flashing Green: Inverter on

Inverter fault

Inverter normal, but off

the load normally

standby

 

 

 

 

 

Bypass

Load on Bypass

Bypass out of

Bypass Normal

power

normal range

 

 

 

 

Load

UPS output on

UPS output

UPS no output power

 

overloaded

 

 

 

 

 

Status

No alarms—UPS

Amber: UPS has a general

UPS has a serious

working normally

alarm

alarm

 

 

*Battery or battery converter abnormal events include these event messages (see Appendix A): No Battery, Battery Replaced, Battery Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.

65

Page 73
Image 73
Emerson 480V Mimic display indicators location, Bypass indicator, Load indicator, Inverter indicator, Rectifier indicator