Table 11 Liebert approved replacement batteries

UPS Specifications

Table 11 Liebert approved replacement batteries

 

Models

Battery Manufacturer

Supplied

 

 

 

HX300

 

 

Enersys Yuasa

HX330

 

HX400

 

 

 

 

HX500

 

 

 

UPS12-100MR

 

 

 

UPS12-150MR

 

 

 

UPS12-210MR

C&D Dynasty

 

UPS12-300MR

 

 

 

UPS12-350MR

 

 

 

UPS12-400MR

 

 

 

UPS12-540MR

 

 

5.4.2DC Intermediate Circuit

Table 12 DC intermediate circuit

Rated Power kVA

40

 

60

80

 

100

 

120

160

 

200

Recommended number

 

Total 40 battery blocks of 12VDC (240 cells of 2VDC)

 

of lead-acid batteries

 

 

 

will be supported by UPS

 

 

 

Recommended float charge voltage

 

 

 

 

2.27VDC *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended boost charge voltage

 

 

 

 

 

2.4VDC *

 

 

 

 

 

 

 

 

 

 

 

 

Recommended end of discharge voltage

 

 

 

1.67 - 1.75 VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum recharge battery current, A *

14.8

 

22.2

29.6

 

37.0

 

44.4

59.2

 

74

 

 

 

 

 

 

 

 

 

 

 

 

Maximum boost charge duration, min. *

 

 

 

 

1800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boost-float threshold current, A *

 

 

 

 

0.1 C default

 

 

 

 

 

 

Temperature voltage compensation, mV/°C *

From 0 to 5 mV/deg. C/cell. Default value is 3mV/deg. C/cell.*

 

 

 

 

 

 

 

 

 

 

 

Ripple voltage superimposed %

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Set by configuration software and based on usage of VLRA batteries.

See Table 8 for current ratings.

5.4.3Inverter Output

Table 13 Inverter output

Rated Power kVA

40

 

60

80

100

120

 

160

 

200

Rated voltage, VAC

 

 

 

 

480

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply

 

 

 

3-phase, 3-wire plus ground

 

 

 

 

 

 

 

 

 

 

 

Frequency, Hz

 

 

 

60 (50Hz in frequency converter mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Power, kW

36

 

54

72

90

108

 

144

 

180

 

 

 

 

 

 

 

 

 

 

 

Three-phase transient

 

 

 

105% to 110% for 60 minutes

 

 

 

 

 

 

111% to 125% for 10 minutes

 

 

 

overload, min. load

 

 

 

 

 

 

 

 

 

126% to 150% for 1 minute

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Regulation %

 

±1.0% three-phase RMS average for a balanced three-phase load

 

 

 

±2.0% three-phase RMS average for a 100% unbalanced load

 

 

 

 

 

Frequency Regulation %

 

 

Nominal frequency regulation is ±0.05% in single module mode,

 

 

 

 

and+/- 0.25% in parallel mode.

 

 

 

 

 

 

 

 

 

 

Maximum rate of change

 

For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s

 

of frequency, Hz/sec

 

 

 

 

 

 

 

 

 

 

 

 

See Table 8 for current ratings.