Table 11 Liebert approved replacement batteries

UPS Specifications

Table 11 Liebert approved replacement batteries

 

Models

Battery Manufacturer

Supplied

 

 

 

HX300

 

 

Enersys Yuasa

HX330

 

HX400

 

 

 

 

HX500

 

 

 

UPS12-100MR

 

 

 

UPS12-150MR

 

 

 

UPS12-210MR

C&D Dynasty

 

UPS12-300MR

 

 

 

UPS12-350MR

 

 

 

UPS12-400MR

 

 

 

UPS12-540MR

 

 

5.4.2DC Intermediate Circuit

Table 12 DC intermediate circuit

Rated Power kVA

40

 

60

80

 

100

 

120

160

 

200

Recommended number

 

Total 40 battery blocks of 12VDC (240 cells of 2VDC)

 

of lead-acid batteries

 

 

 

will be supported by UPS

 

 

 

Recommended float charge voltage

 

 

 

 

2.27VDC *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended boost charge voltage

 

 

 

 

 

2.4VDC *

 

 

 

 

 

 

 

 

 

 

 

 

Recommended end of discharge voltage

 

 

 

1.67 - 1.75 VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum recharge battery current, A *

14.8

 

22.2

29.6

 

37.0

 

44.4

59.2

 

74

 

 

 

 

 

 

 

 

 

 

 

 

Maximum boost charge duration, min. *

 

 

 

 

1800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boost-float threshold current, A *

 

 

 

 

0.1 C default

 

 

 

 

 

 

Temperature voltage compensation, mV/°C *

From 0 to 5 mV/deg. C/cell. Default value is 3mV/deg. C/cell.*

 

 

 

 

 

 

 

 

 

 

 

Ripple voltage superimposed %

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Set by configuration software and based on usage of VLRA batteries.

See Table 8 for current ratings.

5.4.3Inverter Output

Table 13 Inverter output

Rated Power kVA

40

 

60

80

100

120

 

160

 

200

Rated voltage, VAC

 

 

 

 

480

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply

 

 

 

3-phase, 3-wire plus ground

 

 

 

 

 

 

 

 

 

 

 

Frequency, Hz

 

 

 

60 (50Hz in frequency converter mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Power, kW

36

 

54

72

90

108

 

144

 

180

 

 

 

 

 

 

 

 

 

 

 

Three-phase transient

 

 

 

105% to 110% for 60 minutes

 

 

 

 

 

 

111% to 125% for 10 minutes

 

 

 

overload, min. load

 

 

 

 

 

 

 

 

 

126% to 150% for 1 minute

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Regulation %

 

±1.0% three-phase RMS average for a balanced three-phase load

 

 

 

±2.0% three-phase RMS average for a 100% unbalanced load

 

 

 

 

 

Frequency Regulation %

 

 

Nominal frequency regulation is ±0.05% in single module mode,

 

 

 

 

and+/- 0.25% in parallel mode.

 

 

 

 

 

 

 

 

 

 

Maximum rate of change

 

For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s

 

of frequency, Hz/sec

 

 

 

 

 

 

 

 

 

 

 

 

See Table 8 for current ratings.

36

Page 44
Image 44
Emerson 60HZ 5.4.2DC Intermediate Circuit, 5.4.3Inverter Output, Liebert approved replacement batteries, Inverter output

60HZ, 480V specifications

The Emerson 40-120KVA UPS is a high-performing uninterruptible power supply designed to ensure the reliability and continuity of critical operations across various industries. This UPS operates at 480VAC and 60Hz, making it suitable for environments where high-power demands are common.

One of the standout features of this UPS system is its modular design, which allows for easy scalability. Organizations can expand their power capacity as their needs grow, making the Emerson 40-120KVA UPS a future-proof investment. The system operates with high efficiency, minimizing energy consumption and operational costs. This is vital for data centers and industrial applications where energy management is increasingly important.

The Emerson UPS incorporates advanced digital signal processing technology, delivering real-time monitoring and control. This enhances the overall performance and reliability of the system, providing seamless power protection against voltage fluctuations, surges, and interruptions. With a total harmonic distortion of less than 5%, the UPS ensures a clean and stable power output, preserving the integrity of sensitive electronic equipment.

Another noteworthy characteristic of the Emerson 40-120KVA is its redundancy features. The system supports N+1 redundancy, allowing for one extra module to ensure uninterrupted service in case of a failure. This design offers peace of mind for critical applications, ensuring that there is no single point of failure.

User-friendliness is also a significant aspect of the Emerson UPS. The intuitive graphical user interface simplifies monitoring and management, allowing operators to assess system performance and status at a glance. Additionally, remote monitoring capabilities enable real-time tracking of system health and performance from anywhere, providing flexibility and oversight for facility managers.

The Emerson 40-120KVA UPS also meets stringent safety and compliance standards, ensuring reliable operation in demanding environments. Its robust design is suitable for a variety of applications, including information technology, telecommunications, and industrial processes. Overall, the Emerson 40-120KVA UPS stands out as a reliable, efficient, and versatile solution for businesses aiming to safeguard their critical power supply against any disruption.