Figure 49 Buzzer location

Operator Control and Display Panel

8.4Audible Buzzer

The buzzer produces three types of sounds:

Single beep - when any control button is pressed

Single beep repeating every two seconds - the system has a general alarm

Continuous - the system has a serious fault

If the buzzer makes no sound, the system may be operating properly, or an alarm may have been silenced manually.

Figure 49 Buzzer location

Buzzer

LED1

LED2 LED4 LED5

LED3

STATUS

Liebert NX

2007-01-06

09:20:37

 

 

80kVA-3X3

Single

 

Normal

 

 

 

Main

Bypass

Output

 

 

L-N current (A)

L 1-N/L2

L2-N/L3

L3-N/L1

 

 

71.4

70.8

71.3

 

 

Frequency (HZ)

59.9

59.9

59.9

EPO

 

L-L voltage (V)

480

480

480

 

 

 

PowerFactor

0.99

0.99

0.99

INVERTER OFF

FAULT CLEAR

 

 

 

 

 

Input disconnect closed

01-06 09:15

 

 

Output disconnect closed

01-06 09:15

SILENCE ON/OFF

Bypass abnormal

01-06 09:15

 

 

 

 

 

 

?

INVERTER ON

 

 

 

 

 

 

 

F1

F2

F3

F4

HELP

 

 

8.5LCD Overview

The LCD on the front panel has five main sections, as shown in Figure 50. Press the F1 key below the LCD to scroll through these sections.

UPS System Information - view UPS name and model, date and time, overall status (see Table 18).

LCD Menu - choose a category of data items to appear below the menus (see Table 19).

Data and Settings - view data items for the selected menu (see Table 19).

Current Status Messages - check any active UPS event and alarm messages (see Appendix A).

Navigation Key Icons - look at the icon above each navigation key to determine how the key operates when pressed (see 8.6 - Navigation Keys).

The LCD displays alarm information in real time. After appearing in the current status section of the LCD, status messages are stored in the history log—512 records can be stored and retrieved.

Figure 50 Sections of the LCD

 

Liebert NX

2007-01-06

09:20:37

UPS system

LCD menu

80kVA-3X3

Single

 

 

Normal

information

 

Main

Bypass

 

Output

 

 

 

 

L1-N/L2 L2-N/L3

L3-N/L1

 

 

L-N current(A)

71.4

70.8

71.3

 

Data and settings

Frequency(HZ)

59.9

 

59.9

59.9

 

 

L-L voltage(V)

480

 

480

480

 

 

PowerFactor

0.99

 

0.99

0.99

 

Current status

Input disconnect closed

 

01-06 09:15

 

Output disconnect closed

01-06 09:15

 

messages

Bypass abnormal

 

01-06 09:15

Navigation

 

 

 

 

 

 

?

 

F1

F2

F3

 

F4

HELP

key icons

 

 

 

 

 

 

67

 

 

 

 

Page 75
Image 75