Emerson 60HZ, 480V 2.3.1Input Dry Contacts, 2.3.2Maintenance Bypass Cabinet Interface, Table

Models: 60HZ 480V

1 112
Download 112 pages 61.01 Kb
Page 26
Image 26
2.3.1Input Dry Contacts

Electrical Connections

2.3.1Input Dry Contacts

There are several input dry contacts at the X3 slot.

Figure 7 Input dry contacts

+12V +12V

X3

+12V

J4

+12V

GEN

BtG

ENV

J26

GND

+12V

AUX_I

T_IT

J30

AUX_0

T_0T

F_FAN

FUSE

Figure 7 Input dry contactsTable 1Input dry contacts at X3 +12V

J10

OL

GND

FB

DRV

 

 

NOTE: The black square ( ) on each slot indicates Pin 1.

Table 1

Input dry contacts at X3

 

 

 

 

Position

Name

Description

 

 

 

 

 

J4.1

ENV3

Battery Room Alarm (Normally Closed)

 

J4.2

BtG

Battery Ground Fault Detection (Normally Closed)

 

 

 

 

 

J4.3

GEN1,2

Generator Join Detection (Normally Open)

 

J4.4

+12V

+12V Power

 

 

 

 

 

1 - Must be configured using configuration software before becoming active.

2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%). 3 - Activating this feature turns the battery charger off.

2.3.2Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

Table 2 Maintenance bypass cabinet interface

Position

Name

Description

 

 

 

J26.1

T_IT1

Input transformer over temperature (N.C.)

J26.2

AUX_I

Reserved

 

 

 

J26.3

+12V

+12V Power

 

 

 

J26.4

GND

Power Ground

 

 

 

J30.1

FUSE

Reserved

 

 

 

J30.2

F_FAN

Fan Fail Alarm (N.C.)

 

 

 

J30.3

T_OT1

Output Transformer Overtemperature (N.C.)

J30.4

AUX_O

Reserved

 

 

 

1- Must be configured using configuration software before becoming active.

NOTE

All auxillary cables of terminal must be double-insulated. The wire must be 600V, 18-16 AWG stranded for maximum runs between 82 and 197 feet (25-60m), respectively.

18

Page 26
Image 26
Emerson 60HZ, 480V user manual 2.3.1Input Dry Contacts, 2.3.2Maintenance Bypass Cabinet Interface, Input dry contacts, Table