Emerson 60HZ 9.2UPS Startup, 9.1.1Circuit Breakers, 9.2.1Startup Procedure, Circuit breakers

Models: 60HZ 480V

1 112
Download 112 pages 61.01 Kb
Page 86
Image 86
9.1.1Circuit Breakers

Operating Instructions

9.1.1Circuit Breakers

The UPS can be isolated by means of circuit breakers, mounted inside the cabinet and accessible after opening the front door.

The location of the UPS power switches is shown in Figure 59.

Figure 59 Circuit breakers

The UPS unit circuit breakers are CB1, CB2, CB3 and CB5.

CB1—Main Input circuit breaker; connects the utility supply to the UPS main input.

CB2—Bypass circuit breaker; connects the utility supply to the UPS bypass.

CB3—Maintenance Bypass breaker; connects the utility supply to the UPS maintenance bypass.

CB5—Output breaker; connects inverter or bypass to the external output transformer or power distribution panel.

9.2UPS Startup

The Liebert NX must be fully installed and commissioned before startup, and external power isolators must be closed. Once those general conditions are met, the UPS may be started.

9.2.1Startup Procedure

To start the UPS from a fully powered-down condition:

1. Open the UPS door to gain access to the main input circuit breakers.

! WARNING

During this procedure the output terminals will become live.

If any load equipment is connected to the UPS output terminals, please check with the load user and ascertain whether it is safe to apply power to the load. If the load is not ready to receive power, then ensure that it is safely isolated from the UPS output terminals.

2.Close CB1, CB2 and CB3 (CB5 is open).

The main input contactor closes automatically and the LCD begins to show start-up

screens. The Rectifier indicator flashes green while the rectifier is starting up. It stops flashing and becomes solid green about 30 seconds after the rectifier enters the normal operation state.

78

Page 86
Image 86
Emerson 60HZ, 480V user manual 9.2UPS Startup, 9.1.1Circuit Breakers, 9.2.1Startup Procedure, Circuit breakers