9.7Battery Protection

Operating Instructions

9.7Battery Protection

9.7.1Battery Undervoltage Pre-Warning

Before the end of discharge, the Liebert NX displays a Low Battery pre-warning. After this pre-warn- ing, the battery has the capacity for 5 minutes discharging with full load (default time). The Liebert NX can be user-configured to display this warning from 3 to 60 minutes before end-of-discharge.

9.7.2Battery End-of-Discharge (EOD) Protection

If the battery voltage is lower than the end-of-discharge voltage, the battery converter will be shut down.

9.8Multi-Module System Procedures

9.8.1Isolating One Module in a Multi-Module System

1.Turn Off the inverter

2.Open External Output CB4 in Parallel Cabinet (see Figure 60).

The UPS enters Isolation Status automatically, parallel signaling and communication become masked and output becomes inhibited.

3.Power Off the unit for maintenance.

4.Power On the unit.

5.Unit enters Test Mode by configuration software setting.

6.Diagnosis or testing.

7.The UPS exits Test Mode by configuration software setting. Output becomes inhibited because of Isolation Status.

8.Return all switches to the Normal position.

9.Close External Output CB4 in Parallel Cabinet (see Figure 60).

The UPS exits Isolation Status automatically, parallel signaling and communication recovers, output becomes enabled but interlocking works now.

10.Turn On inverter and join the parallel system.

Figure 60 Typical parallel system block diagram with common input supply, with separate batteries and optional output / bypass distribution panel

480V, 3W

System Input

MBB

RIB = Rectifier Input

Breaker

IOB = Inverter Output

Breaker

MBB = Maintenance

Bypass Breaker

MIB = Maintenance

Isolation Breaker

LDB = Load Distribution

Breaker

 

Liebert NX UPS (40-200kVA)

 

 

Bypass

 

 

Static

 

 

Switch

RIB 1

AC

DC

 

 

 

DC

AC

DC

DC

480V DC

Battery Input

RIB 2 9.7.1Battery Undervoltage Pre-Warning9.7.2Battery End-of-Discharge (EOD) ProtectionUPS Module 29.8Multi-Module System Procedures

RIB 3 9.8.1Isolating One Module in a Multi-Module SystemManual backgroundUPS Module 3Manual background

RIB 4 Manual backgroundManual backgroundUPS Module 4Manual background

MIB

IOB 1

IOB 2

IOB 3

IOB 4

480V, 3W Output

LDB 1

User Supplied

Plug-In Output

Breakers

480V, 3W Output

LDB N

NOTE

All equipment servicing procedures must be carried out only by trained personnel.

82

Page 90
Image 90
Emerson 60HZ, 480V 9.7Battery Protection, 9.8Multi-ModuleSystem Procedures, 9.7.1Battery Undervoltage Pre-Warning

60HZ, 480V specifications

The Emerson 40-120KVA UPS is a high-performing uninterruptible power supply designed to ensure the reliability and continuity of critical operations across various industries. This UPS operates at 480VAC and 60Hz, making it suitable for environments where high-power demands are common.

One of the standout features of this UPS system is its modular design, which allows for easy scalability. Organizations can expand their power capacity as their needs grow, making the Emerson 40-120KVA UPS a future-proof investment. The system operates with high efficiency, minimizing energy consumption and operational costs. This is vital for data centers and industrial applications where energy management is increasingly important.

The Emerson UPS incorporates advanced digital signal processing technology, delivering real-time monitoring and control. This enhances the overall performance and reliability of the system, providing seamless power protection against voltage fluctuations, surges, and interruptions. With a total harmonic distortion of less than 5%, the UPS ensures a clean and stable power output, preserving the integrity of sensitive electronic equipment.

Another noteworthy characteristic of the Emerson 40-120KVA is its redundancy features. The system supports N+1 redundancy, allowing for one extra module to ensure uninterrupted service in case of a failure. This design offers peace of mind for critical applications, ensuring that there is no single point of failure.

User-friendliness is also a significant aspect of the Emerson UPS. The intuitive graphical user interface simplifies monitoring and management, allowing operators to assess system performance and status at a glance. Additionally, remote monitoring capabilities enable real-time tracking of system health and performance from anywhere, providing flexibility and oversight for facility managers.

The Emerson 40-120KVA UPS also meets stringent safety and compliance standards, ensuring reliable operation in demanding environments. Its robust design is suitable for a variety of applications, including information technology, telecommunications, and industrial processes. Overall, the Emerson 40-120KVA UPS stands out as a reliable, efficient, and versatile solution for businesses aiming to safeguard their critical power supply against any disruption.