9.9Commissioning a Parallel System

Operating Instructions

9.8.3Shutdown Procedure—Complete UPS and Load Shutdown

This procedure must be followed to completely power down the UPS and the load. All power switches, isolators and circuit breakers will be opened and power will be removed from the load.

In multi-module systems, perform each step of the procedure in every UPS module before proceeding to the next step.

! CAUTION

This procedure will shut off power to the load.

NOTE

Before beginning this procedure, shut down the connected load to prevent the possibility of damage.

1.Press the EPO (Emergency Power Off) button at the UPS front panel only. This will disable Rectifier, Inverter, Static Switch and Battery operation. The load will be de-energized.

! CAUTION

Except in an emergency situation, do not press any remote EPO button

2.Open the UPS door to gain access to the main circuit breakers.

3.Open the Rectifier input circuit breaker CB1.

4.Open external battery circuit breaker. This breaker is inside the battery cabinet or is otherwise adjacent to the battery racks.

5.Open Output circuit breaker CB5.

6.Open bypass input circuit breaker CB2.

7.Ensure maintenance bypass circuit breaker CB3 is open.

8.All mimic panel LED indications and messages will extinguish as the mains-driven, internal power supplies decay.

9.To completely isolate the UPS from the AC supplies, the main external power input isolator (both isolators, where dual supplies are provided for rectifier and bypass) and external output isolator must be opened and tagged with warning labels accordingly.

9.9Commissioning a Parallel System

! CAUTION

The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficulty, call 1-800-LIEBERT for assistance.

Check the input and output wiring of each UPS module. Ensure that the phase rotation sequence of the main inputs and the bypass inputs and outputs of each UPS module are the same. Ensure that the parallel cables are connected firmly.

It is assumed that the installation is complete, the system has been commissioned by authorized per- sonnel and the external power isolators are closed. Disconnect the load before startup.

9.10Parallel System Startup

1.Start each UPS normally as described in 9.2 - UPS Startup

2.Turn on the inverter of each UPS module one at a time.

3.Apply the load after the last UPS module transfers to inverter. The total load can be determined through the LCD of either UPS.

4.Verify the load rate of each UPS module. If the load rates are roughly the same, then the parallel system may be assumed to be operating normally.

NOTE

If one module cannot transfer to inverter mode long after its inverter is on, its output connection may not be good or its output phase rotation may not be coincident with other modules. At this time, the LCD for the UPS module will display “inverter asynchronous” and the inverter indicator will flash continuously. If either UPS module makes abnormal noise after it transfers to inverter, its parallel cables may be incorrectly connected.

84

Page 92
Image 92
Emerson 60HZ, 480V user manual 9.9Commissioning a Parallel System, 9.10Parallel System Startup

60HZ, 480V specifications

The Emerson 40-120KVA UPS is a high-performing uninterruptible power supply designed to ensure the reliability and continuity of critical operations across various industries. This UPS operates at 480VAC and 60Hz, making it suitable for environments where high-power demands are common.

One of the standout features of this UPS system is its modular design, which allows for easy scalability. Organizations can expand their power capacity as their needs grow, making the Emerson 40-120KVA UPS a future-proof investment. The system operates with high efficiency, minimizing energy consumption and operational costs. This is vital for data centers and industrial applications where energy management is increasingly important.

The Emerson UPS incorporates advanced digital signal processing technology, delivering real-time monitoring and control. This enhances the overall performance and reliability of the system, providing seamless power protection against voltage fluctuations, surges, and interruptions. With a total harmonic distortion of less than 5%, the UPS ensures a clean and stable power output, preserving the integrity of sensitive electronic equipment.

Another noteworthy characteristic of the Emerson 40-120KVA is its redundancy features. The system supports N+1 redundancy, allowing for one extra module to ensure uninterrupted service in case of a failure. This design offers peace of mind for critical applications, ensuring that there is no single point of failure.

User-friendliness is also a significant aspect of the Emerson UPS. The intuitive graphical user interface simplifies monitoring and management, allowing operators to assess system performance and status at a glance. Additionally, remote monitoring capabilities enable real-time tracking of system health and performance from anywhere, providing flexibility and oversight for facility managers.

The Emerson 40-120KVA UPS also meets stringent safety and compliance standards, ensuring reliable operation in demanding environments. Its robust design is suitable for a variety of applications, including information technology, telecommunications, and industrial processes. Overall, the Emerson 40-120KVA UPS stands out as a reliable, efficient, and versatile solution for businesses aiming to safeguard their critical power supply against any disruption.