Emerson 480V, 60HZ Auxiliary Dry Contact Cables, For startup procedure, 9.2 - UPS Startup

Models: 60HZ 480V

1 112
Download 112 pages 61.01 Kb
Page 39
Image 39
Auxiliary Dry Contact Cables

Options

Figure 18 Connecting system parallel control cables

1

 

2

UPS

3

 

 

4

 

 

 

 

 

 

Parallel Board

Parallel Board

Parallel Board

Parallel Board

X3

P5

X3

P5

X3

P5

X3

 

P5

 

X4

 

X4

 

X4

 

 

X4

X2-2

X2-1

X2-2

X2-1

X2-2

X2-1

X2-2

X2-1

 

 

 

 

 

 

 

 

Interconnecting

P2

 

P2

 

P2

 

P2

 

Cables

P1

P1

P1

 

P1

X1-1 X1-2

X1-1 X1-2

X1-1 X1-2

X1-1 X1-2

P3

P4

P3

P4

P3

P4

P3

 

P4

Auxiliary Dry Contact Cables

The external output breaker of each UPS must have Normally Open auxiliary contacts. These con- tacts must be wired to connector X3 on the Parallel Logic Board (M3). See Figure 19.

Figure 19 Auxiliary dry contact cables for output breaker in multi-module system

2 X2 P2

1 X2 P1

T INA M T :X

For startup procedure, 9.2 - UPS Startup.Manual backgroundX3

DBSManual backgroundManual background

485- Manual background485+

! CAUTION

The auxiliary control wire must be installed to ensure proper operation of the system.

NOTE

For startup procedure, 9.2 - UPS Startup.

31

Page 39
Image 39
Emerson 480V, 60HZ user manual Auxiliary Dry Contact Cables, For startup procedure, 9.2 - UPS Startup