Several items of optional equipment are available for connection to the Liebert NX UPS.

10.1Communication and Other User Terminals

The UPS can be integrated into advanced networking environments via UPS monitoring software such as Microsoft UPS Monitor, Liebert MultiLink, Liebert Nform, Liebert SiteNet, Modbus / Jbus, Liebert SiteScan, Liebert SiteScan 2, SNMP, etc. They allow UPS status monitoring and automatic and safe shutdown of the server and PCs.

Figure 61 Monitoring board (U2) auxiliary terminal block detail

 

 

J8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J3

J1

 

LCD

 

 

 

 

 

 

 

J22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J23

 

 

 

 

 

 

 

 

 

J12

J2

 

 

 

 

 

 

 

 

J9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J15

 

 

 

 

 

 

 

 

 

J16

 

 

 

 

 

 

 

 

 

J17

 

 

 

 

 

 

 

 

Liebert IntelliSlot 2 X4

J13

J21

J25

J28

J4

J26

J30

J10

Liebert IntelliSlot 1

J24

 

BFP

INV ACF

EPO

Dry in

MBC

BCB

Liebert IntelliSlot 3

 

 

 

 

X1

 

X2

 

X3

 

 

 

 

X7

X6

PWR

 

MODEM

X5

SNMP CARD

X4

NOTE: The black square ( ) on each slot indicates Pin 1.

10.1.1Analog Input Interface

At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is 2 percent. “ENV-T” is used for environment temperature detecting.

X6 pin 1: Not used

X6 pin 2: +12V

X6 pin 3: ENV-T – environment temperature detection

X6 pin 4: GND

10.1.2Power Output

The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to 12V. The maximum current is 500mA.

10.1.3Liebert IntelliSlot Communication

The Liebert NX has three Liebert IntelliSlot ports to allow field-installation of optional communica- tion cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary ESP2 protocol to cards that translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide dry contact signals for external signaling of operating status.

The Liebert IntelliSlot communication ports may be installed or removed while the Liebert NX is operating.