3.5Free-Cooling

Optional Factory-Installed Features - Evaporator/Chilled Water Units

3.5Free-Cooling

Free-cooling option includes separate cooling coil, three-way slow-close valve and separate supply and return piping. Free-cooling is activated when the water temperature reaches a field-adjustable temperature, typically 45°F (7°C). The valve is rated for 300psi (2068kPa) working pressure.

Air-cooled condensing units can be matched with evaporators using free-cooling coils with chilled water sources to serve as backup cooling. When matched with a water/glycol condensing unit, a three-way water regulating valve is recommended for the condensing unit to simplify piping to the main supply pipes. The coil is designed for closed-loop applications using properly treated and circulated fluid. Not available with SCR reheat options.

Figure 7 Free-cooling arrangement

Free-cooling option: A second cooling coil allows the system to take advantage of colder outdoor temperatures and bypass compressor operation.

When the water temperature goes below 45°F (7°C), cooling switches over to free-cooling operation. A separate chilled water source can also be used with air-cooled systems.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundDrycoolerManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Liebert Mini-Mate2

Free -

Cooling

Coil

Water Temperature

Sensor

Water/Glycol

Condenser

Manual backgroundField Piping

NOTE

If free-cooling is applied to an open water tower, an optional copper-nickel (CuNi) coil is required to prevent premature corrosion, or a heat exchanger must separate the tower water from the free-cooling loop. The copper-nickel coil requires an extended lead time.

3.6Optional Configurations—Prop Fan Condensing Units

Outdoor Prop Fan Condensing Units are also available in the following optional configurations:

High ambient, top discharge models for catalog capacities at ambient temperatures up to 105°F (40°C).

Quiet-Line models for low noise level conditions (below 56 dBA) and catalog capacities for ambient temperatures up to 95°F (35°C).

Condenser coil(s) can be phenolic-coated for extended coil life in coastal areas.

3.7Optional Configurations—Water/Glycol Condensing Units

Indoor Water/Glycol Condensing Units are also available with the following piping options:

Two-way water reg. valve with 350 psi (2413kPa) design pressure.

Three-way water reg. valve with 150psi (1034kPa) design pressure.

Three-way water reg. valve with 350psi (2413kPa) design pressure.