Emerson MINI-MATE2 Evaporator unit electrical connections, Site Preparation and Installation

Models: MINI-MATE2

1 72
Download 72 pages 34.22 Kb
Page 31
Image 31
Figure 14 Evaporator unit electrical connections

Site Preparation and Installation

Figure 14 Evaporator unit electrical connections

Earth Ground Connection terminal for field-supplied earth grounding wire

High-Volt Power Connections

Electric service connection terminals

Factory-installed disconnect switch

Remote Humidifier Contact Field-Supplied 24V Class 2 wiring to Terminals 11 & 12, located in field wire compartment

 

Optional Condensate Pump Auxilary Float

 

Switch Connection to Terminal TB1-8 and

 

TB1-9.

 

Heat Rejection Connection. Field

 

supplied 24V NEC class 2 wiring.

 

See Note 2.

 

For remote air cooled units from

Customer Remote Alarm Connection. Field-supplied 24V Class 2 wiring

Terminals TB2-1, 2, 3 & 4 in the

Fan/Coil module to Wires 1, 2, 3 & 4

to connection TB1-1, TB1-2 and TB1-3.

in the condensing module:

Remote Control Panel Connection to TB3-1,2,3,4 connected

1. 24V GND

with field-supplied thermostat wire (22ga, shielded/jacketed:

2. 24V Supply

available from Emerson or others). Unit Control Board

3. High Pressure Alarm (OPT)

terminals marked GND, +5V, T-, T+ must be connected to

4. Hot Gas Bypass Connection

corresponding terminals on Remote Control Wall Box

 

Site Monitoring Connection. Terminals TB4-1(+) TB4-2(-) are for connection

 

of a 2 wire, twisted pair, communication cable (available from Emerson

 

or others) to optional Liebert SiteScan

 

Remote Unit Shutdown. Replace existing jumper between Terminals TB1-4 and TB1-5

Common Alarm Connection.

with normally closed switch having a minimum 75 VA rating. Use field-supplied 24V

Field-supplied 24V Class 2 wiring to

Class 1 wire

common alarm connection TB1-6 and TB1-7.

Field-supplied unit disconnect switch

 

when factory unit disconnect switch

Electric service not by Emerson

is not supplied

Entrance for customer

NOTES:

1. Refer to specification sheet for

high-volt connections

full load amp. and wire size amp.

 

 

ratings.

 

2. Control voltage wiring must be a

 

minimum of 16 GA (1.3mm) for up

 

to 75' (23m) or not to exceed 1 volt

 

drop in control line

Electrical entrance for

 

optional condensate

Drycooler/Circulating pump

pump on back of unit

control circuit TB70-71. Optional

 

w/Econ-O-Cycle models. Use

 

field-supplied 24V Class 2 wire.

Entrance for customer low-voltage connections

Field-supplied, field-wired thermostat wire to remote wall box

Entrance for customer low voltage connections

Field-supplied 24V (NEC Class 2 wiring)

to condensing module (if applicable) DPN000221 Rev. 2