Troubleshooting
11.0TROUBLESHOOTING
Table 25 Troubleshooting
Symptom | Possible Cause | Check Or Remedy | |
|
|
| |
| No power to unit | Check voltage at input terminal block. | |
|
|
| |
| Control voltage circuit breaker (at | Locate short and reset circuit breaker. | |
| transformer) open | ||
|
| ||
| Float switch relay closed | Has rubber band been removed from float switch? Check drain | |
Unit will not start | because of high water in the | and line. Access through left panel. Power must be cycled at the | |
| condensate pan | disconnect to reset. | |
|
| Check terminal | |
| Jumper not in place | Check pins | |
| sensor contact. Check pins | ||
|
| ||
|
| sensor contact. | |
|
|
| |
| Cooling not displayed at the | Adjust TEMP control set point and sensitivity to require cooling. | |
| control panel | ||
|
| ||
| Short cycle prevention control | Control software delays compressor 3 minutes cooling, from stop | |
| to start | ||
|
| ||
| Compressor contactor not pulling | Check for 24 VAC ± 2 VAC at terminals | |
| check contactor. If no voltage at | ||
No cooling | in | ||
terminals | |||
|
|
| |
| Compressor high head pressure | See below for cause. | |
|
|
| |
| Plugged filter/dryer | Replace filter/dryer | |
|
|
| |
|
| Check pressure gauges. At low ambient temperatures, proper | |
| Low refrigerant charge | refrigerant charge is very important on units with | |
|
| receivers. | |
| Insufficient air flow across | Remove debris from coil and air inlets. | |
| condenser coil | ||
Compressor high |
| ||
Water/Glycol Cooled only: No |
| ||
head pressure | Check fluid supply to regulating valve. Adjust valve if necessary. | ||
fluid flowing through condenser | |||
|
| ||
|
|
| |
| Condenser fan not operating | Check fan operation. | |
|
|
| |
| DIP switch not set to enable | See DIP switch settings Table 24. | |
| humidifier option | ||
|
| ||
| “HUMIDIFY” not displayed at | Increase humidity control set point and sensitivity to require | |
| control panel | humidification. | |
|
| Check voltage at | |
| Defective board | ± 2 VAC. If no voltage, check wiring and/or replace board. Check | |
|
| wiring from control panel to board. | |
Humidifier does |
|
| |
| Humidity display will indicate dashes. Check wiring from | ||
not operate | Failed humidity sensor | temperature/humidity board to the control board and from the | |
| wall box to the control board. Replace wallbox or | ||
|
| ||
|
| temperature/humidity circuit board (if remote). | |
|
|
| |
|
| Make sure switch is in Run position. Check humidifier water | |
| No water flow | supply (including filter screen) and check nylon overflow line if | |
|
| canister is full. | |
| Canister fill rate is not keeping up | Check fill valve screen opening and capillary tube for | |
| with the steam output | obstructions. Check water supply pressure (minimum 10 PSIG). | |
| DIP switch not set to enable | See DIP switch settings Table 24. | |
| reheat option | ||
|
| ||
| HEAT not displayed at the | Increase temperature set point to require heating. | |
Reheat will not | control panel | ||
| |||
operate |
|
| |
Reheat safety open, defective | Check voltage at | ||
| 2 VAC. If voltage, check reheat contactor and reheat safety. If no | ||
| reheat contact or defective board | ||
| voltage, check wiring and/or replace board. | ||
|
| ||
|
|
| |
| Element is burned out | Turn off power. Check element continuity with an Ohmmeter. | |
|
|
|
Liebert® | 64 |