Total refrigerant = Units and Lines*

Site Preparation and Installation

Total refrigerant = Units and Lines*

Table 11 Refrigerant charge

 

Model #

R-407C, oz (kg)

 

 

 

60Hz

 

50Hz

 

 

 

 

 

 

 

MM*60E

 

MM*59E

4 (0.11)

 

 

 

 

MM*60K

 

MM*59K

4 (0.11)

 

 

 

 

 

MC*65A

 

MC*64A

432

(12.3)

 

 

 

 

 

MC*69W

 

MC*68W

94

(2.7)

 

 

 

 

 

PFH067A-_L7

 

PFH066A-_L7

426

(12.1)

 

 

 

 

 

PFH067A-_H7

 

PFH066A-_H7

827

(23.4)

 

 

 

 

 

PFHZ67A-_L7

 

PFHZ66A-_L7

827

(23.4)

 

 

 

 

 

All evaporator units and condensing units are fully factory-charged with refrigerant. If field-supplied refrigerant piping is installed, refrigerant must be added; refer to Table 12 to determine the additional charge.

Table 12 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube

Line Size,

R-407C, lb/100 ft. (kg/30m)

 

 

 

O.D., in.

Liquid Line

Suction Line

 

 

 

 

3/8

3.7

(1.7)

1/2

6.9

(3.1)

 

 

 

5/8

11.0 (5.0

0.4 (0.2)

3/4

15.7 (7.1)

0.6 (0.3)

 

 

 

 

7/8

23.0

(10.4)

1.0 (0.4)

 

 

 

1-1/8

1.7 (0.7)

1-3/8

2.7 (1.1)

 

 

 

 

Quick Connect Fittings

NOTE

When hard piping is used, complete all piping and evacuate lines before connecting quick connects.

Be especially careful when connecting the quick connect fittings. Read through the following steps before making the connections.

1.Remove protector caps and plugs.

2.Carefully wipe coupling seats and threaded surfaces with a clean cloth.

3.Lubricate the male diaphragm and synthetic rubber seal with refrigerant oil.

4.Thread the coupling halves together by hand to insure that the threads mate properly.

5.Tighten the coupling body hex nut and union nut with the proper size wrench until the coupling bodies “bottom out” or until a definite resistance is felt.

6.Using a marker or pen, make a line lengthwise from the coupling union nut to the bulkhead.

7.Tighten the nuts an additional quarter-turn; the misalignment of the lines shows how much the coupling has been tightened. This final quarter-turn is necessary to insure that the joint will not leak. Refer to Table 13 for torque requirements.

Table 13 Refrigerant quick connect sizes and torque

Size O.D.

Coupling

Torque

Cu

Size

lb-ft

 

 

 

1/2”

#10

35-45

 

 

 

1-1/8”

#12

50-65

 

 

 

21