Emerson MINI-MATE2 user manual 6.9Setup Operation, 6.9.1Restart Time Delay, 6.9.2C/F Degrees

Models: MINI-MATE2

1 72
Download 72 pages 34.22 Kb
Page 48
Image 48
6.9Setup Operation

Microprocessor Control

6.9Setup Operation

Selecting Setpoint/Setup from the Main Menu will display the following selections:

RESTART TIME DELAY

C/F DEGREES

HUMIDITY CONTROL METHOD

SHOW DIPSWITCH

CW FLUSH

VALVE TIME

Use the Up and Down arrows to scroll through the submenu. Press Enter to select a particular function.

6.9.1Restart Time Delay

This function delays unit restart after main power is restored to the unit. If several systems are operating, the time delays should be set to different values to cause a sequential start. Delay can be set from 0.1 minutes to 9.9 minutes (6 seconds to 594 seconds). Setting the value to zero (0) will prevent the unit from restarting when power is restored. In this case, the unit must be restarted manually by pressing the “ON/OFF” button on the keypad.

6.9.2C/F Degrees

The control may be selected to show readings and setpoints in either degrees Fahrenheit (°F) or Celsius (°C). To change the value use Enter to select this function, then use the Up and Down arrows to change the value. Press Enter to store the value.

6.9.3Humidity Control Method

The operator may select either relative (direct) or absolute (predictive) humidity control. If “relative” is selected, the RH control is taken directly from the RH sensor. If “absolute” is selected, the RH control is automatically adjusted whenever return air temperature deviates from the desired temperature setpoint (i.e., predictive humidity control). The LCD display will indicate percentage relative humidity for both methods of control. If the “absolute” feature is selected, the adjusted humidity reading will also be shown. When utilizing the predictive humidity control feature, the humidity level is automatically adjusted ~2% RH for each degree difference between the return air temperature and the temperature setpoint.

Unnecessary dehumidification can result when overcooling occurs during a dehumidification cycle. This is due to a higher than normal RH reading caused by overcooling the room (about 2% RH for each degree of overcooling). This drop in temperature extends the dehumidification cycle. Later, when the dehumidification ends and the temperature rises to the setpoint, the RH reading falls. The final RH reading will then be lower than actually desired. If the temperature drop was significant enough, the percentage RH could be low enough to activate the humidifier.

If the absolute humidity control is selected, over-dehumidification may be avoided. When overcooling occurs (i.e., causing an increase in the RH reading) the humidity control program estimates what the RH will be when the dehumidification cycle ends and temperature returns to the setpoint. This allows the dehumidification cycle to end at the proper time. Predictive humidity control can greatly reduce energy consumption by minimizing both compressor/reheat operation. Use the UP or DOWN arrow key to select the desired humidity control method.

6.9.4Show DIP Switch

This function shows the position of the DIP switches, which are located on the control board in the unit; 1 = Switch is “ON” and 0 = Switch is “OFF.” For more information on the DIP switches and their functions, see Table 20.

Liebert® Mini-Mate2

42

Page 48
Image 48
Emerson MINI-MATE2 user manual 6.9Setup Operation, 6.9.1Restart Time Delay, 6.9.2C/F Degrees, 6.9.3Humidity Control Method